1-90
A
<.
550-UH User’s Manual
Parameters
0308
ALARM WORD 1
-
1
-
• When an alarm is active, the corresponding bit for the active alarm is set in the Alarm Words.
• Each alarm has a dedicated bit allocated within Alarm Words.
• Bits remain set until the whole alarm word is reset. (Reset by writing zero to the word.)
• The control panel displays the word in hex. For example, all zeros and a 1 in Bit 0 displays as 0001. All zeros and
a 1 in Bit 15 displays as 8000.
0309
ALARM WORD 2
-
1
-
• See parameter 0308.
Group 03: Actual Signals
Code Description Range
Resolution
Default
S
Bit #
0308,
ALARM
WORD
1
0309,
ALARM
WORD
2
0
OVERCURRENT
Reserved
1
OVERVOLTAGE
PID SLEEP
2
UNDERVOLTAGE
ID RUN
3
DIR LOCK
Reserved
4
IO COMM
START ENABLE 1 MISSING
5
AI1 LOSS
START ENABLE 2 MISSING
6
AI2 LOSS
EMERGENCY STOP
7
PANEL LOSS
ENCODER ERROR
8
DEVICE OVERTEMP
FIRST START
9
MOTOR TEMP
Reserved
10
Reserved
USER LOAD CURVE
11
MOTOR STALL
START DELAY
12
AUTORESET Reserved
13
AUTOCHANGE Reserved
14
PFA I LOCK
Reserved
15
Reserved
Reserved
Summary of Contents for Johnson Controls AYK550-UH
Page 2: ......
Page 8: ...1 8 A 550 UH User s Manual Table of contents ...
Page 32: ...1 32 A 550 UH User s Manual Installation ...
Page 66: ...1 66 A 550 UH User s Manual Application macros ...
Page 186: ...1 186 A 550 UH User s Manual Parameters ...
Page 333: ...A 550 UH User s Manual 1 333 Technical data ...