![ABB Johnson Controls AYK550-UH User Manual Download Page 301](http://html.mh-extra.com/html/abb/johnson-controls-ayk550-uh/johnson-controls-ayk550-uh_user-manual_3352301.webp)
A
<.
550-UH User’s Manual
1-301
Technical data
Ratings, 500…600 volt drives
Abbreviated column headers are described in
below.
Symbols
Sizing
The current ratings are the same regardless of the supply voltage within one voltage
range. To achieve the rated motor power given in the table, the rated current of the
drive must be higher than or equal to the rated motor current.
Note 1:
The ratings apply in ambient temperature of 40 °C (104 °F).
Type Code
Normal Use
Frame Size
A
<.
550-xx-
see below
I
2n
A
P
n
HP
Three-phase supply voltage,
500
…
600 V
-02A7-6
2.7
2
R2
-03A9-6
3.9
3
R2
-06A1-6
6.1
5
R2
-09A0-6
9
7.5
R2
-011A-6
11
10
R2
-017A-6
17
15
R2
-022A-6
22
20
R3
-027A-6
27
25
R3
-032A-6
32
30
R4
-041A-6
41
40
R4
-052A-6
52
50
R4
-062A-6
62
60
R4
-077A-6
77
75
R6
-099A-6
99
100
R6
-125A-6
125
125
R6
-144A-6
144
150
R6
Typical ratings:
Normal use
(10% overload capability)
I
2n
continuous rms current. 10% overload is allowed for one minute in ten minutes.
P
n
typical motor power in normal use. The kilowatt power ratings apply to most IEC, 4-pole
motors. The Horsepower ratings apply to most 4-pole NEMA motors.
1 min.
I
n
1,1x
I
n
9 min.
1 min.
Summary of Contents for Johnson Controls AYK550-UH
Page 2: ......
Page 8: ...1 8 A 550 UH User s Manual Table of contents ...
Page 32: ...1 32 A 550 UH User s Manual Installation ...
Page 66: ...1 66 A 550 UH User s Manual Application macros ...
Page 186: ...1 186 A 550 UH User s Manual Parameters ...
Page 333: ...A 550 UH User s Manual 1 333 Technical data ...