1-176
A
<.
550-UH User’s Manual
Parameters
• The table below shows the A
<.
550 PFA motor assignments for some typical settings in the Relay Output
parameters (1401…1403 and 1410…1412), where the settings are either =31 (
PFA
), or =X (anything but 31), and
where the Autochange function is disabled (8118
AUTOCHNG
INTERV
= 0.0).
• The table below shows the A
<.
550 PFA motor assignments for some typical settings in the Relay Output
parameters (1401…1403 and 1410…1412), where the settings are either =31 (
PFA
), or =X (anything but 31), and
where the Autochange function is enabled (8118
AUTOCHNG
INTERV
= value > 0.0).
8118
AUTOCHNG INTERV
-0.1…336.0 h
0.1 h
0.0 h (
NOT
SEL
)
Controls operation of the Autochange function and sets the
interval between changes.
• The Autochange time interval only applies to the time when
the speed regulated motor is running.
• See parameter 8119
AUTOCHNG
LEVEL
for an overview of the
Autochange function.
• The drive always coasts to stop when autochange is
performed.
• Autochange enabled requires parameter 8120
INTERLOCKS
= value > 0.
-0.1 =
TEST
MODE
– Forces the interval to value 36…48 s.
0.0 =
NOT
SEL
– Disables the Autochange function.
0.1…336 – The operating time interval (the time when the
start signal is on) between automatic motor changes.
WARNING!
When enabled, the Autochange function
requires the interlocks (8120
INTERLOCKS
= value > 0)
enabled. During autochange the power output is
interrupted and the drive coasts to stop, preventing
damage to the contacts.
Group 81: PFA Control
Code Description Range
Resolution
Default
S
Parameter setting
A
<.
550 Relay assignment
1
4
0
1
1
4
0
2
1
4
0
3
1
4
1
0
1
4
1
1
1
4
1
2
8
1
1
7
Autochange disabled
RO1
RO2
RO3
RO4
RO5
RO6
31 X X X X X 1
Aux.
X
X
X
X
X
31 31 X X X X 2
Aux.
Aux.
X
X
X
X
31 31 31 X X X 3
Aux.
Aux.
Aux.
X
X
X
X 31 31 X X X 2
X
Aux.
Aux.
X
X
X
X X X 31 X 31 2
X
X
X
Aux.
X
Aux.
31 31 X X X X 1*
Aux.
Aux.
X
X
X
X
* = One additional relay output for the PFA that is in use. One motor is in “sleep”
when the other is rotating.
Parameter setting
A
<.
550 Relay assignment
1
4
0
1
1
4
0
2
1
4
0
3
1
4
1
0
1
4
1
1
1
4
1
2
8
1
1
7
Autochange enabled
RO1
RO2
RO3
RO4
RO5
RO6
31 31 X X X X 1
PFA
PFA
X
X
X
X
31 31 31 X X X 2
PFA
PFA
PFA
X
X
X
X 31 31 X X X 1
X
PFA
PFA
X
X
X
X X X 31 X 31 1
X
X
X
PFA
X
PFA
31 31 X
X
X
X 0**
PFA
PFA
X
X
X
X
** = No auxiliary motors, but the autochange function is in use. Working as a
standard PID-control.
PFA with Autochange mode
A
<.
550
Relay logic
Summary of Contents for Johnson Controls AYK550-UH
Page 2: ......
Page 8: ...1 8 A 550 UH User s Manual Table of contents ...
Page 32: ...1 32 A 550 UH User s Manual Installation ...
Page 66: ...1 66 A 550 UH User s Manual Application macros ...
Page 186: ...1 186 A 550 UH User s Manual Parameters ...
Page 333: ...A 550 UH User s Manual 1 333 Technical data ...