1-170
A
<.
550-UH User’s Manual
Parameters
6408
PEAK TIME 2
Time hh.mm.ss
2 s
-
Time of the peak value detection.
• Format: hours:minutes:seconds.
6409
CURRENT AT PEAK
0.0…6553.5 A
0.1 A
-
Current at the moment of the peak value (amperes).
6410
UDC AT PEAK
0…65535 V
1 V
-
DC voltage at the moment of the peak value (volts).
6411
FREQ AT PEAK
0.0…6553.5 Hz
0.1 Hz
-
Output frequency at the moment of the peak value (herzes).
6412
TIME OF RESET 1
Date dd.mm.yy /
1 d
-
power-on time in days
Last reset date of the peak logger and amplitude logger 2.
• Format: Date if the real time clock is operating (dd.mm.yy). / The number of days elapsed after the power-on if the
real time clock is not used, or was not set (xx d).
6413
TIME OF RESET 2
Time hh.mm.ss
2 s
-
Last reset time of the peak logger and amplitude logger 2.
• Format: hours:minutes:seconds.
6414
AL1RANGE0TO10
0.0…100.0%
0.1%
-
Amplitude logger 1 (current in percent of nominal current
I
2n
) 0…10% distribution.
6415
AL1RANGE10TO20
0.0…100.0%
0.1%
-
Amplitude logger 1 (current in percent of nominal current
I
2n
) 10…20% distribution.
6416
AL1RANGE20TO30
0.0…100.0%
0.1%
-
Amplitude logger 1 (current in percent of nominal current
I
2n
) 20…30% distribution.
6417
AL1RANGE30TO40
0.0…100.0%
0.1%
-
Amplitude logger 1 (current in percent of nominal current
I
2n
) 30…40% distribution.
6418
AL1RANGE40TO50
0.0…100.0%
0.1%
-
Amplitude logger 1 (current in percent of nominal current
I
2n
) 40…50% distribution.
6419
AL1RANGE50TO60
0.0…100.0%
0.1%
-
Amplitude logger 1 (current in percent of nominal current
I
2n
) 50…60% distribution.
6420
AL1RANGE60TO70
0.0…100.0%
0.1%
-
Amplitude logger 1 (current in percent of nominal current
I
2n
) 60…70% distribution.
6421
AL1RANGE70TO80
0.0…100.0%
0.1%
-
Amplitude logger 1 (current in percent of nominal current
I
2n
) 70…80% distribution.
6422
AL1RANGE80TO90
0.0…100.0%
0.1%
-
Amplitude logger 1 (current in percent of nominal current
I
2n
) 80…90% distribution.
6423
AL1RANGE90TO
0.0…100.0%
0.1%
-
Amplitude logger 1 (current in percent of nominal current
I
2n
) over 90% distribution.
6424
AL2RANGE0TO10
0.0…100.0%
0.1%
-
Amplitude logger 2 (signal selection with parameter 6404) 0…10% distribution.
6425
AL2RANGE10TO20
0.0…100.0%
0.1%
-
Amplitude logger 2 (signal selection with parameter 6404) 10…20% distribution.
6426
AL2RANGE20TO30
0.0…100.0%
0.1%
-
Amplitude logger 2 (signal selection with parameter 6404) 20…30% distribution.
Group 64: Load Analyzer
Code Description Range
Resolution
Default
S
Summary of Contents for Johnson Controls AYK550-UH
Page 2: ......
Page 8: ...1 8 A 550 UH User s Manual Table of contents ...
Page 32: ...1 32 A 550 UH User s Manual Installation ...
Page 66: ...1 66 A 550 UH User s Manual Application macros ...
Page 186: ...1 186 A 550 UH User s Manual Parameters ...
Page 333: ...A 550 UH User s Manual 1 333 Technical data ...