![ABB Johnson Controls AYK550-UH User Manual Download Page 314](http://html.mh-extra.com/html/abb/johnson-controls-ayk550-uh/johnson-controls-ayk550-uh_user-manual_3352314.webp)
1-314
A
<.
550-UH User’s Manual
Technical data
Recommendation for conductor layout
The following figure compares conductor layout features in motor cables.
Effective motor cable screens
The general rule for cable screen effectiveness is: the better and tighter the cable’s
screen, the lower the radiated emission level. The following figure shows an
example of an effective construction (for example Ölflex-Servo-FD 780 CP,
Lappkabel or MCCMK, NK Cables).
EN 61800-3 compliant motor cables
To comply with EN 61800-3
requirements:
•
Motor cables must have an effective screen as described in
•
Motor cable screen wires must be twisted together into a bundle (the bundle
length must be less than five times its width) and connected it to the terminal
marked
(at the bottom right-hand corner of the drive).
•
Motor cables must be grounded, at the motor end, with an EMC cable gland. The
ground must contact the cable screen all the way around the cable.
•
For EN 61800-3 First Environment, Restricted Distribution (CISPR11 Class A),
and EN 61800-3 Second Environment compliance, the drive includes an internal
filter that provides compliance for at least 30 m (100 ft.) motor cable lengths. For
some drives, longer cable lengths require an additional, external RFI/EMC filter
as specified in the table below. The RFI/EMC filters are separate options and
Symmetrical shielded cable: three phase
conductors and a concentric or otherwise
symmetrically constructed PE conductor, and a
shield
Recommended
(CE & C-Tick)
PE
Conductor
and Shield
A separate PE conductor is required if the
conductivity of the cable shield is < 50% of the
conductivity of the phase conductor.
Not allowed for motor cables
(CE & C-Tick)
Shield
PE
PE
Allowed for motor cables
with phase
conductor cross section up to 10 mm
2
.
A four-conductor system: three phase
conductors and a protective conductor, without a
shield.
Allowed
(CE & C-Tick)
Shield
Shield
Insulation Jacket
Braided Metallic Screen
Inner Insulator
L1
L2
L3
Summary of Contents for Johnson Controls AYK550-UH
Page 2: ......
Page 8: ...1 8 A 550 UH User s Manual Table of contents ...
Page 32: ...1 32 A 550 UH User s Manual Installation ...
Page 66: ...1 66 A 550 UH User s Manual Application macros ...
Page 186: ...1 186 A 550 UH User s Manual Parameters ...
Page 333: ...A 550 UH User s Manual 1 333 Technical data ...