![ABB Johnson Controls AYK550-UH User Manual Download Page 158](http://html.mh-extra.com/html/abb/johnson-controls-ayk550-uh/johnson-controls-ayk550-uh_user-manual_3352158.webp)
1-158
A
<.
550-UH User’s Manual
Parameters
4023
PID SLEEP LEVEL
0.0…500.0 Hz /
0.1 Hz /
0.0 Hz /
0…30000 rpm
1 rpm
0 rpm
Sets the motor speed / frequency that enables the PID sleep
function – a motor speed / frequency below this level, for at
least the time period 4024
PID
SLEEP
DELAY
enables the PID
sleep function (stopping the drive).
• Requires 4022 = 7 (
INTERNAL
).
• See the figure: A = PID output level; B = PID process
feedback.
4024
PID SLEEP DELAY
0.0…3600.0 s
0.1 s
60.0 s
Sets the time delay for the PID sleep function – a motor speed / frequency below 4023
PID
SLEEP
LEVEL
for at least
this time period enables the PID sleep function (stopping the drive).
• See 4023
PID
SLEEP
LEVEL
above.
Group 40: Process PID Set 1
Code Description Range
Resolution
Default
S
Start
t < P 4024
t > P 4024
Stop
P 4023
P 4025
P 4026
Setpoint
A
B
t
t
P 4025
Setpoint
P 4025
C
D
}
}
4005 = 1
4005 = 0
t
P 4025
Setpoint
P 4025
C
D
P 4026
E
F
P 4026
t
Summary of Contents for Johnson Controls AYK550-UH