1-212
A
<.
550-UH User’s Manual
Embedded fieldbus
N2 binary output objects
The following table lists the N2 Binary Output objects defined for the A
YK
550 drive.
1. N2 LOCAL CTL and N2 LOCAL REF have priority over drive input terminals. Use these binary
outputs for temporary N2 control of the drive when
COMM
is not the selected control source.
DDL file for NCU
The listing below is the Data Definition Language (DDL) file for A
YK
550 drives used
with the Network Control Units.
This listing is useful when defining drive I/O objects to the Network Controller Units.
Below is the A
YK
550.DDL file listing.
*******************************************************************
* ABB Drives, A
:,
550 Variable Frequency Drive
*******************************************************************
CSMODEL "A
:,
_550","VND"
AITITLE "Analog_Inputs"
BITITLE "Binary_Inputs"
AOTITLE "Analog_Outputs"
BOTITLE "Binary_Outputs"
N2 Binary Outputs:
Number
Object
Drive Parameter
Range
BO1
STOP/START
Command Word
0 = Stop, 1 = Start to Speed
BO2
FORWARD/REVERSE
Command Word
0 = Forward, 1 = Reverse
BO3
PANEL LOCK
Command Word
0 = Open, 1 = Locked
BO4
RUN ENABLE
Command Word
0 = Enable, 1 = Disable
BO5
REF1/REF2 SELECT
Command Word
0 = Ref1, 1 = Ref2
BO6
FAULT RESET
Command Word
Change 0 -> 1 Resets
BO7
COMMAND RO 1
134 (bit mask 01)
0 = Off, 1 = On
BO8
COMMAND RO 2
134 (bit mask 02)
0 = Off, 1 = On
BO9
COMMAND RO 3
134 (bit mask 04)
0 = Off, 1 = On
BO10
COMMAND RO 4
134 (bit mask 08)
0 = Off, 1 = On
BO11
COMMAND RO 5
134 (bit mask 10)
0 = Off, 1 = On
BO12
COMMAND RO 6
134 (bit mask 20)
0 = Off, 1 = On
BO13
RESET RUN TIME
114 (indirectly)
0 = N/A, 1 = On (Reset Run Time)
BO14
RESET KWH COUNT
115 (indirectly)
0 = N/A, 1 = On (Reset kWh Count)
BO15
PRC PID SELECT
4027 (indirectly)
0 = SET2, 1 = SET2
BO16
N2 LOCAL CTL (Note 1)
Command Word
0 = Auto, 1 = N2
BO17
N2 LOCAL REF (Note 1)
Command Word
0 = Auto, 1 = N2
BO18
SAVE PARAMETERS
1607 (indirectly)
0 = N/A, 1 = On (Save Parameters)
BO19
READ MAILBOX
0 = No, 1 = Yes
BO20
WRITE MAILBOX
0 = No, 1 = Yes
Summary of Contents for Johnson Controls AYK550-UH
Page 2: ......
Page 8: ...1 8 A 550 UH User s Manual Table of contents ...
Page 32: ...1 32 A 550 UH User s Manual Installation ...
Page 66: ...1 66 A 550 UH User s Manual Application macros ...
Page 186: ...1 186 A 550 UH User s Manual Parameters ...
Page 333: ...A 550 UH User s Manual 1 333 Technical data ...