![ABB Johnson Controls AYK550-UH User Manual Download Page 258](http://html.mh-extra.com/html/abb/johnson-controls-ayk550-uh/johnson-controls-ayk550-uh_user-manual_3352258.webp)
1-258
A
<.
550-UH User’s Manual
Embedded fieldbus
Reference scaling
ABB drives and DCU profiles
The following table describes
REFERENCE
scaling for the
JCI
Drives profile.
Note:
The setting of parameter 1104
REF
1
MIN
and 1107
REF
2
MIN
has no effect on
the scaling of references.
When parameter 1103
REF
1
SELECT
or 1106
REF
2
SELECT
is set to
COMM
+
AI
1 or
COMM
*
AI
1, the reference is scaled as follows:
ABB Drives and DCU Profiles
Reference
Range
Reference
Type
Scaling
Remarks
REF1
-32767
…
+32767
Speed or
frequency
-20000 = -
(par. 1105)
0 = 0
+20000 =
(par. 1105)
(20000 corresponds to 100%)
Final reference limited by
1104/1105. Actual motor
speed limited by 2001/2002
(speed) or 2007/2008
(frequency).
REF2
-32767
…
+32767
Speed or
frequency
-10000 = -
(par. 1108)
0 = 0
+10000 =
(par. 1108)
(10000 corresponds to 100%)
Final reference limited by
1107/1108. Actual motor
speed limited by 2001/2002
(speed) or 2007/2008
(frequency).
Torque
-10000 = -
(par. 1108)
0 = 0
+10000 =
(par. 1108)
(10000 corresponds to 100%)
Final reference limited by
2015/2017 (torque1) or 2016/
2018 (torque2).
PID
Reference
-10000 = -
(par. 1108)
0 = 0
+10000 =
(par. 1108)
(10000 corresponds to 100%)
Final reference limited by
4012/4013 (PID set1) or
4112/4113 (PID set2).
ABB Drives and DCU Profiles
Reference
Value
Setting
AI Reference Scaling
REF1
COMM
+
AI
1
COMM
(%) +(
AI
(%) - 0.5*
REF
1
MAX
(%))
0%
50%
(100 + 0.5 * (Par. 1105)%
(100 - 0.5 * (par. 1105))%
100%
100%
AI1 Input Signal
Fieldbus Reference
Correction Coefficient
Summary of Contents for Johnson Controls AYK550-UH
Page 2: ......
Page 8: ...1 8 A 550 UH User s Manual Table of contents ...
Page 32: ...1 32 A 550 UH User s Manual Installation ...
Page 66: ...1 66 A 550 UH User s Manual Application macros ...
Page 186: ...1 186 A 550 UH User s Manual Parameters ...
Page 333: ...A 550 UH User s Manual 1 333 Technical data ...