1-150
A
<.
550-UH User’s Manual
Parameters
If you want to emulate the behavior of an old underload curve with parameters as in
the shaded columns, set the new parameters as in the white columns in the two
tables below:
Underload supervision with
parameters 3013…3015 (obsolete)
Obsolete parameters
New parameters
3013
UNDERLOAD
FUNCTION
3014
UNDERLOAD
TIME
3701
USER
LOAD
C
MODE
3702
USER
LOAD
C
FUNC
3703
USER
LOAD
C
TIME
No underload functionality
0
-
0
-
-
Underload curve, fault generated
1
t
1
1
t
Underload curve, alarm generated
2
t
1
2
2 · t
Obs. par.
New parameters
3015
UNDERLOAD
CURVE
3704
LOAD
FREQ
1
(Hz)
3705
LOAD
TORQ
LOW
1
(%)
3707
LOAD
FREQ
2
(Hz)
3708
LOAD
TORQ
LOW
2
(%)
3710
LOAD
FREQ
3
(Hz)
3711
LOAD
TORQ
LOW
3
(%)
3713
LOAD
FREQ
4
(Hz)
3714
LOAD
TORQ
LOW
4
(%)
3716
LOAD
FREQ
5
(Hz)
3717
LOAD
TORQ
LOW
5
(%)
1
6
10
38
17
50
23
60
30
500
30
2
6
20
37
30
50
40
60
50
500
50
3
6
30
37
43
50
57
60
70
500
70
4
6
10
88
17
117
23
144
30
500
30
5
6
20
86
30
119
40
144
50
500
50
Summary of Contents for Johnson Controls AYK550-UH
Page 2: ......
Page 8: ...1 8 A 550 UH User s Manual Table of contents ...
Page 32: ...1 32 A 550 UH User s Manual Installation ...
Page 66: ...1 66 A 550 UH User s Manual Application macros ...
Page 186: ...1 186 A 550 UH User s Manual Parameters ...
Page 333: ...A 550 UH User s Manual 1 333 Technical data ...