![ABB Johnson Controls AYK550-UH User Manual Download Page 72](http://html.mh-extra.com/html/abb/johnson-controls-ayk550-uh/johnson-controls-ayk550-uh_user-manual_3352072.webp)
1-72
A
<.
550-UH User’s Manual
Parameters
Group 22: ACCEL/DECEL
2201
ACC
/
DEC
1/2
SEL
-6…7
1
0 (
NOT
SEL
)
2202
ACCELER
TIME
1
0.0…1800.0 s
0.1 s
30.0 s
2203
DECELER
TIME
1
0.0…1800.0 s
0.1 s
30.0 s
2204
RAMP
SHAPE
1
0.0…1000.0 s
0.1 s
0.0 s (
LINEAR
)
2205
ACCELER
TIME
2
0.0…1800.0 s
0.1 s
60.0 s
2206
DECELER
TIME
2
0.0…1800.0 s
0.1 s
60.0 s
2207
RAMP
SHAPE
2
0.0…1000.0 s
0.1 s
0.0 s
2208
EMERG
DEC
TIME
0.0…1800.0 s
0.1 s
1.0 s
2209
RAMP
INPUT
0
-6…7
1
0 (
NOT
SEL
)
Group 23: SPEED CONTROL
2301
PROP
GAIN
0.00…200.00
0.01
3.00
2302
INTEGRATION
TIME
0.00…600.00 s
0.01 s
0.50 s
2303
DERIVATION
TIME
0…10000 ms
1 ms
0 ms
2304
ACC
COMPENSATION
0.00…600.00 s
0.01 s
0.00 s
2305
AUTOTUNE
RUN
0, 1
1
0 (
OFF
)
Group 25: CRITICAL SPEEDS
2501
CRIT
SPEED
SEL
0, 1
1
0 (
OFF
)
2502
CRIT
SPEED
1
LO
0.0…500.0 Hz / 0…30000 rpm
0.1 Hz / 1 rpm 0.0 Hz / 0 rpm
2503
CRIT
SPEED
1
HI
0.0…500.0 Hz / 0…30000 rpm
0.1 Hz / 1 rpm 0.0 Hz / 0 rpm
2504
CRIT
SPEED
2
LO
0.0…500.0 Hz / 0…30000 rpm
0.1 Hz / 1 rpm 0.0 Hz / 0 rpm
2505
CRIT
SPEED
2
HI
0.0…500.0 Hz / 0…30000 rpm
0.1 Hz / 1 rpm 0.0 Hz / 0 rpm
2506
CRIT
SPEED
3
LO
0.0…500.0 Hz / 0…30000 rpm
0.1 Hz / 1 rpm 0.0 Hz / 0 rpm
2507
CRIT
SPEED
3
HI
0.0…500.0 Hz / 0…30000 rpm
0.1 Hz / 1 rpm 0.0 Hz / 0 rpm
Group 26: MOTOR CONTROL
2601
FLUX
OPT
ENABLE
0, 1
1
1 (
ON
)
2602
FLUX
BRAKING
0, 1
1
0 (
OFF
)
2603
IR
COMP
VOLT
0.0…100.0 V
0.1 V
0.0 V
2604
IR
COMP
FREQ
0…100%
1%
80%
2605
U
/
F
RATIO
1, 2
1
2 (
SQUARED
)
2606
SWITCHING
FREQ
1, 2, 4, 8, 12 kHz
-
4 kHz
2607
SWITCH
FREQ
CTRL
0, 1
1
1 (
ON
)
2608
SLIP
COMP
RATIO
0…200%
1%
0%
2609
NOISE
SMOOTHING
0, 1
1
0 (
DISABLE
)
2619
DC
STABILIZER
0, 1
1
0 (
DISABLE
)
Group 29: MAINTENANCE TRIG
2901
COOLING
FAN
TRIG
0.0…6553.5 kh, 0.0 disables
0.1 kh
0.0 kh
2902
COOLING
FAN
ACT
0.0…6553.5 kh
0.1 kh
0.0 kh
2903
REVOLUTION
TRIG
0…65535 Mrev, 0 disables
1 Mrev
0 Mrev
2904
REVOLUTION
ACT
0…65535 Mrev
1 Mrev
0 Mrev
2905
RUN
TIME
TRIG
0.0…6553.5 kh, 0.0 disables
0.1 kh
0.0 kh
2906
RUN
TIME
ACT
0.0…6553.5 kh
0.1 kh
0.0 kh
2907
USER
MWh
TRIG
0.0…6553.5 MWh, 0.0 disables
0.1 MWh
0.0 MWh
2908
USER
MWh
ACT
0.0…6553.5 MWh
0.1 MWh
0.0 MWh
Code
Name
Range
Resolution
Default
User
S
Summary of Contents for Johnson Controls AYK550-UH
Page 2: ......
Page 8: ...1 8 A 550 UH User s Manual Table of contents ...
Page 32: ...1 32 A 550 UH User s Manual Installation ...
Page 66: ...1 66 A 550 UH User s Manual Application macros ...
Page 186: ...1 186 A 550 UH User s Manual Parameters ...
Page 333: ...A 550 UH User s Manual 1 333 Technical data ...