550-UH User’s Manual
1-139
Parameters
3405
OUTPUT1 UNIT
0…127
1
121 (%SP)
Selects the units used with the first display parameter.
Note:
Parameter is not effective if parameter 3404
OUTPUT
1
DSP
FORM
= 9 (
DIRECT
).
3406
OUTPUT1 MIN
Depends on selection
-
0.0 (%SP)
Sets the minimum value displayed for the first display parameter.
Note:
Parameter is not effective if parameter 3404
OUTPUT
1
DSP
FORM
= 9 (
DIRECT
).
3407
OUTPUT1 MAX
Depends on selection
-
1000.0 (%SP)
Sets the maximum value displayed for the first display parameter.
Note:
Parameter is not effective if parameter 3404
OUTPUT
1
DSP
FORM
= 9 (
DIRECT
).
3408
SIGNAL2 PARAM
100…178
1
104 (
CURRENT
)
Selects the second parameter (by number) displayed on the control panel. See parameter 3401.
3409
SIGNAL2 MIN
Depends on selection
-
0.0 A
Defines the minimum expected value for the second display parameter. See parameter 3402.
3410
SIGNAL2 MAX
Depends on selection
-
2.0 ·
I
2n
A
Defines the maximum expected value for the second display parameter. See parameter 3403.
3411
OUTPUT2 DSP FORM
0…9
1
9 (
DIRECT
)
Defines the decimal point location for the second display parameter. See parameter 3404.
3412
OUTPUT2 UNIT
0…127
1
1 (A)
Selects the units used with the second display parameter. See parameter 3405.
3413
OUTPUT2 MIN
Depends on selection
-
0.0 A
Sets the minimum value displayed for the second display parameter. See parameter 3406.
3414
OUTPUT2 MAX
Depends on selection
-
2.0 ·
I
2n
A
Sets the maximum value displayed for the second display parameter. See parameter 3407.
3415
SIGNAL3 PARAM
100…178
1
120 (
AI
1)
Selects the third parameter (by number) displayed on the control panel. See parameter 3401.
3416
SIGNAL3 MIN
Depends on selection
-
0.0%
Defines the minimum expected value for the third display parameter. See parameter 3402.
3417
SIGNAL3 MAX
Depends on selection
-
100.0%
Defines the maximum expected value for the third display parameter. See parameter 3403.
3418
OUTPUT3 DSP FORM
0…9
1
5 (+0.0)
Defines the decimal point location for the third display parameter. See parameter 3404.
Group 34: Panel Display
Code Description Range
Resolution
Default
S
0 =
NO
UNIT
9 = °C
18 = MWh
27 = ft
36 = l/s
45 = Pa
54 = lb/m
63 = Mrev
1 = A
10 = lb ft
19 = m/s
28 = MGD
37 = l/min
46 = GPS
55 = lb/h
64 = d
2 = V
11 = mA
20 = m
3
/h
29 = inHg
38 = l/h
47 = gal/s
56 = FPS
65 = inWC
3 = Hz
12 = mV
21 = dm
3
/s
30 = FPM
39 = m
3
/s
48 = gal/m
57 = ft/s
66 = m/min
4 = %
13 = kW
22 = bar
31 = kb/s
40 = m
3
/m
49 = gal/h
58 = inH
2
O
67 = Nm
5 = s
14 = W
23 = kPa
32 = kHz
41 = kg/s
50 = ft
3
/s
59 = in wg
68 = Km
3
/h
6 = h
15 = kWh
24 = GPM
33 = ohm
42 = kg/m
51 = ft
3
/m
60 = ft wg
7 = rpm
16 = °F
25 = PSI
34 = ppm
43 = kg/h
52 = ft
3
/h
61 = lbsi
8 = kh
17 = hp
26 = CFM
35 = pps
44 = mbar
53 = lb/s
62 = ms
The following units are useful for the bar display.
117 = %ref
119 = %dev
121 = % SP
123 = Iout
125 = Fout
127 = Vdc
118 = %act
120 = % LD
122 = %FBK 124 = Vout
126 = Tout
Summary of Contents for Johnson Controls AYK550-UH
Page 2: ......
Page 8: ...1 8 A 550 UH User s Manual Table of contents ...
Page 32: ...1 32 A 550 UH User s Manual Installation ...
Page 66: ...1 66 A 550 UH User s Manual Application macros ...
Page 186: ...1 186 A 550 UH User s Manual Parameters ...
Page 333: ...A 550 UH User s Manual 1 333 Technical data ...