22
Electrical commissioning
Installing fieldbus adapter modules (K458,
+K475)
If the inverter is ordered with fieldbus options, the fieldbus modules are installed at the
factory. Use these steps, if you change or order a fieldbus adapter afterwards.
WARNING!
Obey the safety instructions on page
. If you ignore the
instructions, physical injury or death, or damage to the equipment can
occur.
1. Disconnect the inverter
from the supply, lock out the disconnecting device, and
measure to make sure that there is no voltage present. Refer to
.
2. Switch off any potentially dangerous control voltages coming to the inverter.
3. Install the module into slot 1 of the control unit (see details on the
Hardware manual
page
104
).
4. Push the retaining clip on top of the module to lock it.
5. Tighten the mounting screw of the module.
6. Connect the necessary wiring to the module and obey the instructions in the
documentation of the module.
7. Configure the module. Refer to the instructions in the documentation of the module as
well as the appropriate firmware manual.