Maintenance 47
Replacing DC fuses
WARNING!
Obey the safety instructions on page
. If you ignore the
instructions, physical injury or death, or damage to the equipment can
occur.
1. Before you start, stop the inverter and do the steps in
2. Use wind hooks on the doors.
3. If the inverter has fuse status detection option, remove and disconnect the cables
related to it on the fuse.
4. Grease the fuse rails.
5. Replace the blade fuses using the supplied fuse handle.
6. Make sure that the new fuse is properly pushed to the slot.