Electrical commissioning 21
With internal auxiliary power G415:
1. Open switch -Q64 and prevent accidental closing. Closing the switch can generate
dangerous voltage in the main AC busbars and connected equipment.
2. Connect neutral wire to terminal -X11.
3. Connect line wire to terminal -X12.
4. You can limit the power consumption by opening the 48 V PSU feeding circuit
breakers. Close only -F12 to activate the control boards and communication modules.
Smoke detector
The inverter
is equipped with a smoke detector in the DC section as standard. For more
information, refer to the
Firmware manual
.
Remove the protective cap from the smoke detector during commissioning.