
30
Status indicators
Status display of the control panel
Refer to the
Firmware manual
.
Warning and fault messages
Refer to the
Firmware manual
.
Control unit BCU-12
BATT OK
Green
The battery voltage of the real-time clock is OK
(more than 2.8 V).
When the LED off:
• The battery voltage is less than 2.8 V
• The battery is missing
• The control unit is not powered
PWR OK
Green
The internal voltage is correct.
FAULT
Red
The control program indicates that the equipment is
faulty.
Refer to the
Firmware manual
.
WRITE
Yellow
Writing to SD card in progress.
AC500
PWR
Green
The AC500 unit is powered.
RUN
Green
The AC500 program is running.
ERR
Red
An error or warning detected by the AC500
firmware.
MIRU-01
POWER
Green
The MIRU-01 unit is powered.
ERROR
Red
An error detected by the MIRU-01 firmware.
STATUS
Green
The status of the insulation resistance
measurement:
• Slow flash (once every 5 seconds):
Measurement ready
• Rapid flash (5 times per second):
Measurement not ready
DISABLE
Red
Insulation resistance measurement is disabled.
MGND-01
POWER
Green
The MGND-01 is powered.
GROUNDING
STATUS
Green
The grounding voltage is OK (<50 V DC)
BAMU-11
POWER
Green
The BAMU-11 unit is powered.
LINK FAULT
Red
There is an error on the board or an error in the
PSL2 link.
U2 > 60V
Yellow
The input voltages (U2, V2 and W2) are more than
60 V. Used for DC voltage measurement.
U1 > 60V
Yellow
The input voltages (U1, V1 and W1) are more than
60 V. Used for AC voltage measurement.
Where
LED
Color
Indication
Summary of Contents for Fimer PVS980-58-4348kVA-I
Page 1: ...Central inverter PVS980 58 From 4348 to 5000 kVA Commissioning and maintenance manual ...
Page 4: ...2 ...
Page 16: ...14 Safety instructions ...
Page 20: ...18 Introduction to the manual ...
Page 26: ...24 Electrical commissioning ...
Page 56: ...54 Maintenance ...