82 Communication profiles
10
ABOVE_LIMIT
1
The actual frequency or speed
equals or exceeds supervision
limit (set by the drive parameter).
This is valid in both directions of
rotation.
0
The actual frequency or speed is
within the supervision limit.
11
EXT_CTRL_LOC
1
External Control Location EXT2
selected
Note concerning ACS880:
This
bit is effective only if the fieldbus
interface is set as the target for
this signal by drive parameters.
User bit 0 selection (06.33).
0
External Control Location EXT1
selected
12
EXT_RUN_ENABLE
1
External Run Enable signal
received
Note concerning ACS880:
This
bit is effective only if the fieldbus
interface is set as the target for
this signal by drive parameters.
User bit 1 selection (06.34).
0
No External Run Enable signal
received
13
…14
Reserved
15
FBA_ERROR
1
A communication error is
detected by the adapter module.
0
The fieldbus adapter
communication is OK.
Bit
Name
Value
Description