Communication profiles 81
Status word contents
The table below shows the contents of the Status word for the ABB
Drives communication profile. The upper case boldface text refers
to the states shown in the state machine on page
.
Bit
Name
Value
Description
0
RDY_ON
1
READY TO SWITCH ON
0
NOT READY TO SWITCH ON
1
RDY_RUN
1
READY TO OPERATE
0
OFF1 ACTIVE
2
RDY_REF
1
OPERATION ENABLED
0
OPERATION INHIBITED
3
TRIPPED
1
FAULT
0
No fault
4
OFF_2_STA
1
OFF2 inactive
0
OFF2 ACTIVE
5
OFF_3_STA
1
OFF3 inactive
0
OFF3 ACTIVE
6
SWC_ON_INHIB
1
SWITCH-ON INHIBITED
0
-
7
ALARM
1
Warning / alarm
0
No warning / alarm
8
AT_SETPOINT
1
OPERATION
.
The actual value equals
reference = is within tolerance
limits, ie, the speed control,
speed error is 10% max of the
nominal motor speed.
0
The actual value differs from
reference = is outside tolerance
limits.
9
REMOTE
1
Drive control location: REMOTE
(EXT1 or EXT2)
0
Drive control location: LOCAL
Summary of Contents for FECA-01 EtherCAT
Page 1: ...Options for ABB drives converters and inverters User s manual FECA 01 EtherCAT adapter module ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 14: ...14 Safety instructions ...
Page 28: ...28 Mechanical installation ...
Page 32: ...32 Electrical installation ...
Page 63: ...Start up 63 ...
Page 66: ...66 Start up ...
Page 86: ...86 Communication profiles ...