![ABB FECA-01 EtherCAT User Manual Download Page 125](http://html.mh-extra.com/html/abb/feca-01-ethercat/feca-01-ethercat_user-manual_2715125.webp)
Appendix A – CoE Object Dictionary 125
603F
Error code
U16
R
Tx CiA 402 error code of
the last error which
occurred in the drive.
Values according to
IEC 61800-7-201.
Manufacturer-specific
error codes
0xFF00...0xFFFF: In
general, all drive fault
codes from 0xFF00
and above pass
straight through into
this object. Two error
codes are generated
by the adapter mod-
ule:
• 0xFFE1: Failed to
read fault code
from the drive.
• 0xFFFF: Unhan-
dled drive fault
code - correspond-
ing CiA 402 error
code does not ex-
ist.
See object 2201 and
the drive manual.
6040
Controlword U16
RW
Rx CiA 402 control word
6041
Statusword
U16
R
Tx CiA 402 status word
6042
vl target ve-
locity
I16
RW
Rx Effective in the vl
operation mode
6043
vl velocity
demand
I16
R
Tx Operational if the
ramp function genera-
tor output is available
from the drive. Cyclic
low priority communi-
cation.
Note:
Not available
with ACS355.
Index SI
Name
Type
Ac-
cess
PM
Information
NVS
Summary of Contents for FECA-01 EtherCAT
Page 1: ...Options for ABB drives converters and inverters User s manual FECA 01 EtherCAT adapter module ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 14: ...14 Safety instructions ...
Page 28: ...28 Mechanical installation ...
Page 32: ...32 Electrical installation ...
Page 63: ...Start up 63 ...
Page 66: ...66 Start up ...
Page 86: ...86 Communication profiles ...