![ABB FECA-01 EtherCAT User Manual Download Page 108](http://html.mh-extra.com/html/abb/feca-01-ethercat/feca-01-ethercat_user-manual_2715108.webp)
108 Appendix A – CoE Object Dictionary
1601
0 RxPDO 2 map
U8
RW
Number of mapped ob-
jects (0...8).
Write access in the
PREOP state only.
FBA
1 -
U32
RW
Rx PDO 2 mapping en-
try 1.
Value 0x60400010 =
object 6040 Control-
word, length 16 bits.
FBA
2 -
U32
RW
Rx PDO 2 mapping en-
try 2.
Value 0x607A0020 =
object 607A Target po-
sition, length 32 bits.
FBA
… …
U32
RW
Value 0 = none
FBA
8 -
U32
RW
Rx PDO 2 mapping en-
try 8.
Value 0 = none.
FBA
1602
0 RxPDO 3 map
U8
RW
Number of mapped ob-
jects (0...8).
Write access in the
PREOP state only.
FBA
1 -
U32
RW
Rx PDO 3 mapping en-
try 1.
Value 0x60400010 =
object 6040 Control-
word, length 16 bits.
FBA
2 -
U32
RW
Rx PDO 3 mapping en-
try 2.
Value 0x60FF0020 =
object 60FF Target ve-
locity, length 32 bits.
FBA
… …
U32
RW
Value 0 = none
FBA
8 -
U32
RW
Rx PDO 3 mapping en-
try 8.
Value 0 = none.
FBA
Index SI Name
Type
Ac-
cess
Information
NVS
Summary of Contents for FECA-01 EtherCAT
Page 1: ...Options for ABB drives converters and inverters User s manual FECA 01 EtherCAT adapter module ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 14: ...14 Safety instructions ...
Page 28: ...28 Mechanical installation ...
Page 32: ...32 Electrical installation ...
Page 63: ...Start up 63 ...
Page 66: ...66 Start up ...
Page 86: ...86 Communication profiles ...