130 Appendix A – CoE Object Dictionary
607B
0 Position
range limit
U8
R
Modulo values for the
position command val-
ue. When the limits
are exceeded, the
command value wraps
around to the other
end of the range.
Modulo calculation is
disabled when both
limit values are zeros.
1 Min posi-
tion range
limit
I32
RW
Minimum input posi-
tion data value.
Default: 0
FBA
2 Max posi-
tion range
limit
I32
RW
Maximum input posi-
tion data value.
Default: 0
FBA
607C
Home offset
I32
RW
Offset from zero point
to home position.
Default: 0.
Note
: New values are
activated in homing
mode only.
FBA
607D
0 Software
position lim-
it
U8
R
Saturation limit val-
ues for the position
command value
1 Min posi-
tion limit
I32
RW
Default: -2
31
FBA
2 Max posi-
tion limit
I32
RW
Default: 2
31
- 1
FBA
6081
Profile ve-
locity
U32
RW
Velocity normally at-
tained at the end of
the acceleration ramp
during a profiled
move. Cyclic low pri-
ority communication.
Drv
Index SI
Name
Type
Ac-
cess
PM
Information
NVS
Summary of Contents for FECA-01 EtherCAT
Page 1: ...Options for ABB drives converters and inverters User s manual FECA 01 EtherCAT adapter module ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 14: ...14 Safety instructions ...
Page 28: ...28 Mechanical installation ...
Page 32: ...32 Electrical installation ...
Page 63: ...Start up 63 ...
Page 66: ...66 Start up ...
Page 86: ...86 Communication profiles ...