![ABB FECA-01 EtherCAT User Manual Download Page 77](http://html.mh-extra.com/html/abb/feca-01-ethercat/feca-01-ethercat_user-manual_2715077.webp)
Communication profiles 77
The following figure describes the state machine of the CiA 402
communication profile.
CW: xxxxxxxx1xxxxxxx
From any state
FAULT REACTION
ACTIVE
SW: xxxxxxxxx0xx1111
Fault reaction
completed
FAULT
SW: xxxxxxxxx0xx1000
START
Power-on,
self-initialization
NOT READY
SW: xxxxxxxxx0xx0000
TO SWITCH ON
Initialized
successfully
CW: xxxxxxxxxxxxx01x
CW: xxxxxxxxxxxxx110
CW: xxxxxxxxxxxxx110
CW: xxxxxxxxxxxxx111
CW: xxxxxxxxxxxxx01x
or
CW: xxxxxxxxxxxxxx0x
CW: xxxxxxxxxxxx0111
CW: xxxxxxxxxxxx1111
CW: xxxxxxxxxxxxx110
Quick stop
completed
CW: xxxxxxxxxxxxx01x
CW: xxxxxxxxxxxxxx0x
CW: Control word
SW: Status word
SWITCH ON
SW: xxxxxxxxx1xx0000
DISABLED
SWITCHED ON
SW: xxxxxxxxx01x0011
READY TO
SW: xxxxxxxxx01x0001
SWITCH ON
OPERATION
SW: xxxxxxxxx01x0111
ENABLED
QUICK STOP
SW: xxxxxxxxx0xx0111
ACTIVE
or
CW: xxxxxxxxxxxxxx0x
or
CW: xxxxxxxxxxxxxx0x
State transition
(0)
(1)
(15)
(2)
(7)
(3)
(6)
(10)
(12)
(9)
(8)
(5)
(4)
(11)
(13)
(14)
Summary of Contents for FECA-01 EtherCAT
Page 1: ...Options for ABB drives converters and inverters User s manual FECA 01 EtherCAT adapter module ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 14: ...14 Safety instructions ...
Page 28: ...28 Mechanical installation ...
Page 32: ...32 Electrical installation ...
Page 63: ...Start up 63 ...
Page 66: ...66 Start up ...
Page 86: ...86 Communication profiles ...