description. Data objects include configuration properties, that contain cross-referencing
information between protocol and the OPC/IEC 61850.
Process data is connected to a Gateway client using a Cross-References function available
in the client IED object. Data objects that are transferred to the client are dragged from
the servers on the structure to the function tool. Cross-referencing information is filled
in the function window. The Cross-References function supports import and export with
Microsoft Excel.
When the structure is complete and all the objects have been set up properly the config-
uration is downloaded to COM600 using the Gateway Management function available
on the Gateway object.
The Logic Processor function is programmed with a separate programming editor.
Recommended Maximum Configuration
6.3.
We have analyzed the recommended maximum configuration for COM600 for IEC61850
Communication with HMI and Data Historian configured.
Based on this configuration we recommend the following amount of connected IEDs or
maximun load of 90 load units, as shown in the table below.
Load Unit
IED Count
IED Family
1,5
60
611 series
2
45
615 series
3
30
620 series
1
90
630 series
1
90
670 series
It is also recommended not to exceed the amount of 30 IEDs per IEC 61850 OPC Server
Instance.
Configuration process
6.4.
Overview of configuration process
6.4.1.
Before you can start using COM600, build and configure the communication and substa-
tion structure of your project in SAB600.
Start SAB600 and open and name a project.
49
COM600 series, version 4.1
1MRS756125
User's Manual