Standard
Description
According to IEC 60529
Degree of protection by
enclosure
According to IEC 60255-5
Clearance and creepage dis-
tances
Table 4.1-8 Power supply and module tests
Standard
Description
According to IEC 60255-1
Auxiliary voltage
According to IEC 60255-11
Aux. voltage interruptions
According to IEC 60255-11 15%, f = 2 x fn
Ripple in auxiliary DC voltage
According to CE EN 61010
Power consumption
Table 4.1-9 Insulation tests
Standard
Description
According to IEC 60255-5 2 kV, 50 Hz for 1 minute
Dielectric test
According to IEC 60255-5 5 kV, 1.2/50 μs, 0.5 J
Impulse voltage test
According to IEC 60255-5 >100 MΩ, 500 Vdc
Insulation resistance
According to IEC 60255-27 <0.1 Ω.
Protective bonding impedance
The EMC immunity test level meets the requirements listed below:
Table 4.1-10 Electromagnetic compatibility tests
Standard
Description
According to IEC 61000-4-18 and IEC 60255-22-1
•
2.5 kV
•
1.0 kV
1 MHz and 100 kHz burst dis-
turbance test
•
Common mode
•
Differential mode
According to IEC 61000-4-2, IEC 60255-22-2
•
6 kV
•
8 kV
Electrostatic discharge test
•
Contact discharge
•
Air discharge
According to IEC 61000-4-3 and IEC 60255-22-3
•
10 V/m (80% amp.mod.)
•
f=80...2700 MHz
•
10 V/m (pulse mod.) f=900 MHz
Radio frequency field immunity
According to IEC 61000-4-4 and IEC 60255-22-4
•
2 kV
•
1 kV
Fast transient
•
Power supply
•
RJ-45 port
According to IEC 61000-4-5 and IEC 60255-22-5
•
2 kV line-to-earth, 1 kV line-to-line
Surge immunity
•
Power supply
31
COM600 series, version 4.1
1MRS756125
User's Manual
Summary of Contents for COM600 series
Page 1: ...COM600 series version 4 1 User s Manual...
Page 2: ......
Page 6: ...6...
Page 103: ......