SCLImport_communicationOptions.png
Figure 6.4.2.6-3 Communication options
You can select the following options:
•
Filter Data Objects that don't belong to DataSet: By selecting this option,
you can enhance performance. This option limits the amount of data objects
being created in SAB600, meaning that if a data object does not belong to any
data set, it will not be created in to the SAB600. Some IEDs can provide large
amounts of data that is not reported (that is, not updated) in COM600 HMI.
•
Overwrite existing descriptions: This option overwrites all existing descriptions
of objects affected by the import operation.
Select this option only if you know that the imported
file contains better descriptions than your current
configuration.
•
Import protocol configuration (sAddr): When selecting this option, both the
object tree and protocol configuration will be created. If you do not select this
option, only the object tree structure will be created.
•
Overwrite Limit settings: This option overwrites all configured unit and limit
configurations and assigns them values from the SCL file.
57