Standard
Description
According to IEC 61000-4-6 and IEC 60255-22-6
•
10 V (80% ampl. mod.)
•
f= 150 kHz...80 MHz
Conducted radio frequency
disturbance
According to IEC 61000-4-8, 300 A/m, continuous
Power frequency (50 Hz) mag-
netic field
According to IEC 61000-4-11
•
30% reduction for 10 ms
•
60% reduction for 100 ms
•
60% reduction for 1000 ms
•
>95% reduction for 5000 ms
Voltage dips and short interrup-
tions
According to EN 55011, and IEC60255-25, class A
Emission tests
Table 4.1-11 Environmental conditions
Value
Description
-25...+70ºC
1) 2)
Operating temperature range
5...95% at +40ºC
Relative humidity range, non-
condensing
-40...+70ºC
Storage temperature
1) Without any option cards
2) With Ethernet option card: 0…+55°C, with Serial option card: 0…+55°C, with LON option card:
0…+70°C
Table 4.1-12 Environmental tests
Standard
Description
According to IEC 60068-2-2
Test values:
•
96 h at +55ºC
•
4 h at +70ºC
Dry heat test
According to IEC 60068-2-1
Test values:
•
96 h at -10ºC
•
4 h at -25ºC
Cold test
According to IEC 60068-2-30
Test values:
•
6 cycles (12+12h) at +25…55°C, humidity >93%
Damp heat test, cyclic
32
1MRS756125
COM600 series, version 4.1
User's Manual
Summary of Contents for COM600 series
Page 1: ...COM600 series version 4 1 User s Manual...
Page 2: ......
Page 6: ...6...
Page 103: ......