Before installing the breaker, the secondary
disconnects must be wired to the Emax 2
Retrofill Breaker.
Wires with wire markers are provided on the
breaker. Make sure that the switchgear
wiring connection points match up with the
original wiring of the cubicle. This ensures
that all wiring connections are properly
made.
Wrong connections will cause the breaker to
malfunction.
WIRING
Notice
AKD-10: Install Accessories
This section deals with installing and wiring the legacy secondary disconnect assemblies
onto the Emax 2 Retrofill breaker. Installing the secondary disconnect assembly consists
of doing these tasks:
Figure 36
AKD-10 Secondary Disconnects View 1
26 - AKD-10: Secondary Disconnects
Installing the secondary disconnect assembly (Figure 36, Figure 37, and
Figure 38).
Wiring the secondary disconnect assembly (Table 6 shows the WavePro
secondary disconnect terminals).
The Emax 2 Retrofill Breaker has these three options:
One secondary disconnect installed
Two secondary disconnects installed
No secondary disconnects installed
NOTE: Wires shall be routed below the vented cover (Fig. 36) and wire tied to the
side
frames, do not route wires over arcchutes, allow slack in wires so secondary
disconnect sits level and lifted by the spring washer (Fig. 38).
C
Summary of Contents for AKD-10
Page 36: ...11 14 22 21 31 34 42 41 C2 C1 51 54 62 61 71 74 82 81 91 94 02 01 45 48 R1 R2 C ...
Page 38: ...C ...
Page 43: ...NOTES 1 WP WavePro fixed connection point C ...
Page 51: ...ONLY for 3200A Figure 48 Steps in Exploded Views for 3200A WPS 32 WPH 32 WPX 32 C ...
Page 52: ...ONLY for 3200A Figure 49 Steps in Exploded Views for 4000A WPS 40 WPX 40 C ...
Page 53: ...Figure 50 Steps in Exploded Views for 5000A WPS 50 WPX 50 ONLY for 3200A C ...
Page 65: ...Figure 64 Wiring of WP 4000A breaker with FAN control unit C ...
Page 74: ...Figure 75 Figure 76 WPF 16 with special 2500A Fuse WPF 16 2500A Fuse Tang Positions 74 C ...