Hold the bottom finger subassembly in place.
Place two fingers around the bolt from the top, hooking the fingers into the
main retainer. Then place a bow-tie spacer in each finger and hold them in
position
with a pressure plate retainer.
Place a spring, bushing, and flat washer over the bolt, then secure with the two
nuts.
Repeat Steps 7 through 13 for each set of fingers.
Adjust the nut to get a spacing of 0.766 - 0.797 inch between the top of the upper
retainer and the bottom of the flat washer.
Tighten the jam nut to lock in the adjustment.
Clean finger assemblies, if necessary, with a clean, lint-free rag and isopropyl
alcohol or acetone.
Be sure to apply a thin film of Mobilgrease 28 to the contact areas which slide
onto the switchgear stabs (See Figure 42, Step 2).
For 1600A & 2000A
For 800A
Figure 42
Steps for working with the primary contacts for 800A, 1600A and 2000A