Remove existing compartment door(s) and remove hinge block using #2 Phillips headed
screw driver.
To install new door follow the instructions below:
De-energize/switch off the LVS section that is to be retrofitted
Open the compartment door that is to be retrofitted.
Rack out the existing legacy AKR breaker from the LVS.
Keep the door open for accessing the door mounting pads placed on the right side
wall in the LVS compartment.
Loosen the screws holding the mounting pads to the compartment frame.
Note that this will provide access for removing the old door from the LVS compartment.
Unpack the new door assembly and mount it on the compartment and secure via
placing the hinges and tightening the screws.
Insert the new retrofitted Emax 2 Retrofill circuit breaker into the compartment and
slide the breaker into the disconnected condition.
Close the new door and secure it to the compartment.
Rack-in the new retrofitted Emax 2 Retrofill circuit breaker.
For ordering the new door depending on door size refer to document
2TSA451008P0000
Install New Door or Door Adaptor
Figure 58
De-energize/switch off the LVS section that is to be retrofitted.
Open the compartment door that is to be retrofitted.
To install OEM Door Adaptor Follow the instructions below
:
C
Summary of Contents for AKD-10
Page 36: ...11 14 22 21 31 34 42 41 C2 C1 51 54 62 61 71 74 82 81 91 94 02 01 45 48 R1 R2 C ...
Page 38: ...C ...
Page 43: ...NOTES 1 WP WavePro fixed connection point C ...
Page 51: ...ONLY for 3200A Figure 48 Steps in Exploded Views for 3200A WPS 32 WPH 32 WPX 32 C ...
Page 52: ...ONLY for 3200A Figure 49 Steps in Exploded Views for 4000A WPS 40 WPX 40 C ...
Page 53: ...Figure 50 Steps in Exploded Views for 5000A WPS 50 WPX 50 ONLY for 3200A C ...
Page 65: ...Figure 64 Wiring of WP 4000A breaker with FAN control unit C ...
Page 74: ...Figure 75 Figure 76 WPF 16 with special 2500A Fuse WPF 16 2500A Fuse Tang Positions 74 C ...