![ABB Advant Controller 450 User Manual Download Page 469](http://html.mh-extra.com/html/abb/advant-controller-450/advant-controller-450_user-manual_3016469.webp)
$GYDQW
&RQWUROOHU8VHU¶V*XLGH
6HFWLRQ$ 6%%DFNXS3RZHU6XSSO\9GF
3BSE 002 415R701 Rev A
A-29
3RZHU6XSSO\RI5$0
Output voltage at normal operation:
5.6 V
±
0.2V (zero load)
Output voltage at backup operation:
6.0 V
±
0.2V
Max. current:
2 A
Notes:
- The output voltage level is raised during backup operation to compensate for voltage drops in voting circuitry.
- The output current is short-circuit proof.
- The physical output has a serial diode to provide two SB511s in parallel operation.
%DWWHU\&KDUJLQJ
Designed to NiCd battery 12 V, 4 Ah., for example, SB522.
Charging current:
,QGLFDWRUV
LEDs on module front:
F, Fault (red)
Low-charging current, low 5 V supply (IP is supposed to indicate converter in operation)
IP, Input Power (green)
Mains supply available, converter in operation
BP, Battery Powered (ylw)
Mains supply not available, discharging of battery
BF, Battery Fault (red)
Discharged/unconnected battery, short-circuit or interruption in battery, cold battery at start
FC, Fast Charging (ylw)
Indicates recharging after power-up or battery replacement (10 hours)
0DLQWHQDQFH3DUWV
Miniature Fuse Link, 5 x 20 mm, 4AF (fast)
ABB part no. 5672 2011-20
0HFKDQLFDO'DWD
Module size: 6 SU, 12 mp (“half height, double width”)
Weight: 0.95 kg (2.1 lbs.)
Block Diagram
Charging
4 Ah 100%
2.8 Ah 70%
Time h
10
30
40
0
m
A
175 mA
175 mA
4AF
SB522
6%
RAM
Processor Module
Normal
5V supply
Mains
Supply
d.c.
4AF
SB522
6%
RAM
Processor Module
Normal
5V supply
Mains
Supply
d.c.
Normal Operation
Charging of Battery
Backup Operation
Discharging of Battery
1
2
X9
PE
PE
1
2
X9
3
3
Summary of Contents for Advant Controller 450
Page 1: ...Advant OCS with Master software GYDQW RQWUROOHU User s Guide 3BSE 002 415R701 Rev A ...
Page 26: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xvi ...
Page 30: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xx ...
Page 488: ... GYDQW RQWUROOHU 8VHU V XLGH SSHQGL DUGZDUH 0RGXOHV A 48 3BSE 002 415R701 Rev A ...
Page 508: ...Advant Controller 450 User s Guide Appendix D Item Designations D 12 3BSE 002 415R701 Rev A ...
Page 518: ...Advant Controller 450 User s Guide Appendix F Load Calculation F 4 3BSE 002 415R701 Rev A ...
Page 522: ...Advant Controller 450 User s Guide Appendix G Memory Calculation G 4 3BSE 002 415R701 Rev A ...
Page 528: ...Advant Controller 450 User s Guide Appendix H Halt Codes H 6 3BSE 002 415R701 Rev A ...
Page 562: ...Advant Controller 450 User s Guide Index iv 3BSE 002 415R701 Rev A ...
Page 563: ......
Page 564: ...3BSE 002 415R701 Rev A March 2000 ...