Advant
®
Controller 450 User’s Guide
Section 2.6.6 Enlargement of the System Software
3BSE 002 415R701 Rev A
2-89
12. Set the start mode selector on the new processor module in the same position as the
existing processor module.
13. Push the ENTER button on the new module.
Check the display. A correct installation gives the following indications in sequence:
a.
b2 (UPGRADING), b1 STANDBY) after
<
90 sec.
b.
LEDs DUAL on both processor modules light up.
The left processor module is now PRIMARY while the new one is BACKUP.
14. Make a basic function test. Manual changeover is described in
15. Give the command DICONFIG. The resulting working modes are:
PRIMARY
P1 OPERATION
STANDBY start in b2 UPGRADING and then transition to b1 STANDBY
The command DICONFIG causes the process control to start!
16. It is recommended that you perform a full scale function test, that is during normal process
control. Manual changeover is described in
.
---------------------------end------------------------
2.6.6 Enlargement of the System Software
Below you can find instructions on how to change a program card with the system software to a
variant with another assembly of program modules, that is another functional assembly.
Revision of system software is dealt with in the same way.
An exchange procedure is assumed. After reception of a new program card, the used one is
returned to the sender.
For a detailed description of the connection and use of an engineering station and different
dump/load commands, see separate documentation, AMPL Configuration Advant
Controller 400 Series.
Preparation and Setup
1.
The new SW is ordered.
A new program card is delivered, including the desired assembly of program modules (or
the new revision).
2.
Enclosed at delivery, you will find a release identification with a compatibility code. (See
Section 1.7.1.1, Version Designation
.) The compatibility code determines whether you
must use data base source code to re-create the application with new system software or if
other alternatives exist.
3.
Check the system software compatibility code in the running system.
This is visible on the engineering station display screen when you log in on the target
system, or it is displayed with the help of the command SHTARG.
Summary of Contents for Advant Controller 450
Page 1: ...Advant OCS with Master software GYDQW RQWUROOHU User s Guide 3BSE 002 415R701 Rev A ...
Page 26: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xvi ...
Page 30: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xx ...
Page 488: ... GYDQW RQWUROOHU 8VHU V XLGH SSHQGL DUGZDUH 0RGXOHV A 48 3BSE 002 415R701 Rev A ...
Page 508: ...Advant Controller 450 User s Guide Appendix D Item Designations D 12 3BSE 002 415R701 Rev A ...
Page 518: ...Advant Controller 450 User s Guide Appendix F Load Calculation F 4 3BSE 002 415R701 Rev A ...
Page 522: ...Advant Controller 450 User s Guide Appendix G Memory Calculation G 4 3BSE 002 415R701 Rev A ...
Page 528: ...Advant Controller 450 User s Guide Appendix H Halt Codes H 6 3BSE 002 415R701 Rev A ...
Page 562: ...Advant Controller 450 User s Guide Index iv 3BSE 002 415R701 Rev A ...
Page 563: ......
Page 564: ...3BSE 002 415R701 Rev A March 2000 ...