![ABB Advant Controller 450 User Manual Download Page 363](http://html.mh-extra.com/html/abb/advant-controller-450/advant-controller-450_user-manual_3016363.webp)
Advant
®
Controller 450 User’s Guide
Section 5.5.2 Diagnostics and Fault Announcement
3BSE 002 415R701 Rev A
5-11
Reference in Advant Cont roller 400 Display:
Present ation:
Function:
Actions at fault:
Block Diagram:
Regulator 1 (2..4)
green
Normal
red cr
Fault - Regulator 1 (2..4) missing or err.
Supervision of particular 5 V regulator in the subrack containing the processor module.
1. Replace the regulator pointed out
Plain System Message
at fault:
(only relevant when redundant 5 V regulators are installed).
Software
DB; AC450
System status OS
Regulator 1
Hardware
REG1_ERR
Y/N REG1
DIAGN.
SR511
PM511
24VA
24VB
24 V distribution
2
1
5 V
3
Controller Power Supply
POW SUPP ST
Voltage Regulator faulty
Net xx
Nod yy
2. See
Section 5.4.9.5, Check of Power Supply
Reference in Advant Cont roller 400 Display:
Present ation:
Function:
Actions at fault:
Block Diagram:
Batt. volt. 2
green
Normal
red cr
Fault
Supervision of the battery charge and the battery condition
1. Replace the Battery Unit SB522
Plain System Message
at fault:
Software
DB; AC450
System status OS
Batt. volt. 2
Hardware
BATT_ERR
Y/N BPS2
DIAGN.
SB522
SB510/511
4
POW SUPP ST
Backup Battery faulty
Net xx
Nod yy
2. See
Section 5.4.9.6, Check of Backup Power Supply
Summary of Contents for Advant Controller 450
Page 1: ...Advant OCS with Master software GYDQW RQWUROOHU User s Guide 3BSE 002 415R701 Rev A ...
Page 26: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xvi ...
Page 30: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xx ...
Page 488: ... GYDQW RQWUROOHU 8VHU V XLGH SSHQGL DUGZDUH 0RGXOHV A 48 3BSE 002 415R701 Rev A ...
Page 508: ...Advant Controller 450 User s Guide Appendix D Item Designations D 12 3BSE 002 415R701 Rev A ...
Page 518: ...Advant Controller 450 User s Guide Appendix F Load Calculation F 4 3BSE 002 415R701 Rev A ...
Page 522: ...Advant Controller 450 User s Guide Appendix G Memory Calculation G 4 3BSE 002 415R701 Rev A ...
Page 528: ...Advant Controller 450 User s Guide Appendix H Halt Codes H 6 3BSE 002 415R701 Rev A ...
Page 562: ...Advant Controller 450 User s Guide Index iv 3BSE 002 415R701 Rev A ...
Page 563: ......
Page 564: ...3BSE 002 415R701 Rev A March 2000 ...