Section 2.5.3 Commissioning
3BSE 002 415R701 Rev A
2-77
•
Analog Output Signals
shows typical analog output channels and where you can test the signals.
Analog output signals in a specific plant are shown in the connection diagrams for the
plant.
Proceed as follows to check analog channels:
–
Use the blocking command (BL) to block any PC programs already entered.
–
Ensure that the data base connections for the output signals concerned are correct.
–
Use the command MDB on the engineering unit to present the element in the data
base, set the VALUE and check that the corresponding output shows this value.
Then measure the value on the screw terminal block of the corresponding connection
unit end and, if practical, at the process as well.
–
When you are checking analog output signals, use a multimeter to test that an output
signal is obtained over the complete signal range.
For a description of adjustment of analog output signals, see
Readjustment of Analog Output Signals
AO boards are factory adjusted for voltage output signals. If current signal is
desired/jumpered, you must readjust for maximum accuracy. Please follow the instructions
given in
Section 5.5.12, Channel Adjustment on AO Board
2.5.3.10 Listing of PC Program and Data Base
When the PC program is entered, you can obtain a printout from the printer connected to the
engineering tool for editing or documentation purposes. Two different types of printout are
available:
•
Printout as a graphic diagram with LPCD (List PC Diagram). See
•
Printout as a program list with LPCL (List PC List). Use this to your advantage when you
need rapid listing of a PC program on a printer or screen and when listing on a printer
without graphic mode. See
.
Use the command LDBD (List Data Base Diagram) to print the data base.
All procedures are described in the manual AMPL Configuration Advant Controller 400 Series.
Summary of Contents for Advant Controller 450
Page 1: ...Advant OCS with Master software GYDQW RQWUROOHU User s Guide 3BSE 002 415R701 Rev A ...
Page 26: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xvi ...
Page 30: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xx ...
Page 488: ... GYDQW RQWUROOHU 8VHU V XLGH SSHQGL DUGZDUH 0RGXOHV A 48 3BSE 002 415R701 Rev A ...
Page 508: ...Advant Controller 450 User s Guide Appendix D Item Designations D 12 3BSE 002 415R701 Rev A ...
Page 518: ...Advant Controller 450 User s Guide Appendix F Load Calculation F 4 3BSE 002 415R701 Rev A ...
Page 522: ...Advant Controller 450 User s Guide Appendix G Memory Calculation G 4 3BSE 002 415R701 Rev A ...
Page 528: ...Advant Controller 450 User s Guide Appendix H Halt Codes H 6 3BSE 002 415R701 Rev A ...
Page 562: ...Advant Controller 450 User s Guide Index iv 3BSE 002 415R701 Rev A ...
Page 563: ......
Page 564: ...3BSE 002 415R701 Rev A March 2000 ...