![ABB Advant Controller 450 User Manual Download Page 209](http://html.mh-extra.com/html/abb/advant-controller-450/advant-controller-450_user-manual_3016209.webp)
Advant
®
Controller 450 User’s Guide
Section 2.4.2 Controller and I/O
3BSE 002 415R701 Rev A
2-55
processor module will be PRIMARY while the right processor module will be
BACKUP.
explains alternative ways of starting.
See
There are also some negative indications, for example:
–
Backup Power Supply SB511 (or SB510)
red LED F (Fault)
red LED BF (Batt. Fault)
(Indicating that battery is not connected)
–
S100 I/O boards
red LED F (Fault)
(Indicating that the boards are not implemented)
–
S100 I/O Bus Extenders DSBC 174 or DSBC 176
yellow LEDs INIT
and INHIB
(Indication that the boards are not implemented)
7.
If a LAN communication interface CS513 exists and if it is addressed and set properly by
on-board switches during the setup (see
), it gives the following
indications:
–
Communication Interface CS513
green LED RUN
ylw LED TX/LAN (flash)
ylw LED RX
(flash)
(Indicating a successful automatic configuration of the LAN communication.)
8.
The target system is now ready for configuration by connecting the engineering station
directly to the processor module service port. If redundant processor modules connect to
the primary module. Configuration is also possible via the network if applicable and
desirable.
9.
Finally, set the start mode selector on Processor Module PM511 in 1 (AUTO) position.
Repeat for an eventually redundant processor module.
WARNING
Do NOT push the ENTER button!
Summary of Contents for Advant Controller 450
Page 1: ...Advant OCS with Master software GYDQW RQWUROOHU User s Guide 3BSE 002 415R701 Rev A ...
Page 26: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xvi ...
Page 30: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xx ...
Page 488: ... GYDQW RQWUROOHU 8VHU V XLGH SSHQGL DUGZDUH 0RGXOHV A 48 3BSE 002 415R701 Rev A ...
Page 508: ...Advant Controller 450 User s Guide Appendix D Item Designations D 12 3BSE 002 415R701 Rev A ...
Page 518: ...Advant Controller 450 User s Guide Appendix F Load Calculation F 4 3BSE 002 415R701 Rev A ...
Page 522: ...Advant Controller 450 User s Guide Appendix G Memory Calculation G 4 3BSE 002 415R701 Rev A ...
Page 528: ...Advant Controller 450 User s Guide Appendix H Halt Codes H 6 3BSE 002 415R701 Rev A ...
Page 562: ...Advant Controller 450 User s Guide Index iv 3BSE 002 415R701 Rev A ...
Page 563: ......
Page 564: ...3BSE 002 415R701 Rev A March 2000 ...