If the board is added off-line because REDIMENSION of the data base was necessary (no
spares available), the following start-up sequence is applicable.
A data base dump DUTDB and a PC program dump DUTPT are presupposed.
1.
Follow the general instructions in
Section 2.6.7, Power-up Ahead of Program Loading
.
2.
Perform the controller system configuration:
a.
Load the data base dump, LOTDB and REDIMENSION.
b.
Create the additional data base, DIMDB.
c.
Perform data entry of additional data base, MDB.
d.
Dump and load (compress) the data base, DUTDB/LOTDB.
e.
Load the PC program dump, LOTPT, and REDIMENSION PC program tables,
if necessary.
3.
Perform configuration/application building:
a.
Populate the additional data base, MDB.
b.
Enter and edit PC program, if relevant.
c.
Dump and load PC programs, DUTPT/LOTPT.
4.
Back up the entire RAM, DUAP.
5.
Disable working mode CONFIGURATION, DICONFIG.
In addition to those indications obtained at power-up:
–
All red LED F (Fault) on S100 I/O board fronts are switched off.
–
The yellow LEDs INIT and INHIB on S100 I/O Bus Extenders DSBC 174/
DSBC 176 board front are switched off.
6.
The processor module changes over and indicates P1 (working mode OPERATION).
The system is now started and ready for operation.
Perform the final stages, which include start of executing application programs, successively,
especially those application programs which are affected by the additional I/O board. Do one
PC program at a time.
WARNING
When the application program is started, the process to be controlled is
influenced.
The significant engineering tool commands you use are:
1.
DIsable Build Mode, DIBM PCx
2.
DeBLock, DBL.
Verification
Make functional tests, including process functions, applicable.
Summary of Contents for Advant Controller 450
Page 1: ...Advant OCS with Master software GYDQW RQWUROOHU User s Guide 3BSE 002 415R701 Rev A ...
Page 26: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xvi ...
Page 30: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xx ...
Page 488: ... GYDQW RQWUROOHU 8VHU V XLGH SSHQGL DUGZDUH 0RGXOHV A 48 3BSE 002 415R701 Rev A ...
Page 508: ...Advant Controller 450 User s Guide Appendix D Item Designations D 12 3BSE 002 415R701 Rev A ...
Page 518: ...Advant Controller 450 User s Guide Appendix F Load Calculation F 4 3BSE 002 415R701 Rev A ...
Page 522: ...Advant Controller 450 User s Guide Appendix G Memory Calculation G 4 3BSE 002 415R701 Rev A ...
Page 528: ...Advant Controller 450 User s Guide Appendix H Halt Codes H 6 3BSE 002 415R701 Rev A ...
Page 562: ...Advant Controller 450 User s Guide Index iv 3BSE 002 415R701 Rev A ...
Page 563: ......
Page 564: ...3BSE 002 415R701 Rev A March 2000 ...