Mechanical installation
■
Connecting the internal cooling circuit to a customer cooling unit
The converter delivery does not include the liquid cooling unit that is to be connected to the
converter cabinet.
Connecting the liquid pipes
Note:
It is recommended to use closing valves in the pipe connections of the cooling circuit.
1. Ensure that there is sufficient space and free access to make proper cooling pipe
connections between the liquid cooling unit and the converter. It is not allowed to use
inflexible and fixed cooling pipe connections between two separate units (eg, liquid
cooling unit and the converter connection). Always use a flexible connector that can
reduce possible stress caused by eg, vibration.
2. Check visually that the converter liquid pipes are not damaged (threads and flange joint
not damaged).
3. Connect the external cooling circuit directly to the coupling pipes on the side of the
converter. Lay liquid piping with extreme care. Secure the pipes properly mechanically
and check for leaks. See the technical data for the pipe materials.
4. Position the liquid pipe ends against each other.
5. Centre the connector onto the pipe ends.
6. Tighten the
• threaded connector carefully and ensure that it is slid on the pipe ends. The use of
appropriate sealant is recommended.
• flange bolts to a minimum torque of 70 N·m (52 lbf·ft).
7. Make sure that the liquid pipes are securely connected.
Filling up and bleeding the internal cooling circuit
Both the converter and coolant must be at room temperature before filling in the cooling
circuit.
WARNING!
Obey these instructions. If you ignore them, injury or death, or damage to the
equipment can occur.
• Use protective eyewear when working with the liquid cooling system.
• Make sure that the maximum permissible operating pressure is not exceeded.
When necessary control the pressure to appropriate level by draining excess
coolant out of the system.
• Do not drain propylene glycol into the sewer system.
• Be careful when you bleed the cooling circuit. Air bubbles in the circuit may
reduce or completely block coolant flow and cause overheating. Fill up and
bleed the pumps in the cooling circuit carefully as they can get damaged when
run dry. Obey the instructions of the external cooling unit.
122 Cooling and heating
Summary of Contents for ACS880-87LC-3200A
Page 2: ......
Page 4: ......
Page 10: ...10 ...
Page 18: ...5 1 3 4 6 8 7 2 18 Safety instructions ...
Page 48: ...48 ...
Page 68: ...68 ...
Page 75: ...b 3 a 2 6 c 4 Air flow direction is towards the converter module Maintenance 75 ...
Page 85: ...14 Open the installation stand optional and place it in front of the module 14 Maintenance 85 ...
Page 108: ...108 ...
Page 112: ...Description CAN bus connection XCAN XCAN 112 BCU x5 control unit ...
Page 116: ...116 Dimension drawings ...
Page 117: ...Dimension drawings 117 ...
Page 118: ...118 Dimension drawings ...
Page 130: ...130 ...