Planning the cooling system
■
Connection to a customer cooling unit
General requirements
Equip the system with an expansion tank to damp pressure rise due to volume changes
when the temperature varies. Keep the pressure within the limits specified in section
. Install a pressure regulator to ensure that the maximum permissible
operating pressure is not exceeded.
Install a bleeding valve at the highest point of the cooling circuit. Bleeding valve is not
included in the ABB converter delivery as standard. It can be ordered as an option (+G422).
The materials used in the cooling system are listed in section
Coolant temperature control
The temperature of the coolant in the internal cooling circuit must be kept within the limits
specified in section
. Note that the minimum temperature depends
on ambient temperature and relative humidity.
The following diagram shows an example of coolant temperature control using the three-way
valve in the external cooling circuit. Part of the infeed coolant flow is directed into the return
pipe through a three-way valve without letting it circulate in the internal cooling circuit if the
coolant in the internal circuit is too cold.
TC
1
2
3
4
Internal circuit
1
External circuit
2
Infeed
3
Return
4
Cooling and heating 121
Summary of Contents for ACS880-87LC-3200A
Page 2: ......
Page 4: ......
Page 10: ...10 ...
Page 18: ...5 1 3 4 6 8 7 2 18 Safety instructions ...
Page 48: ...48 ...
Page 68: ...68 ...
Page 75: ...b 3 a 2 6 c 4 Air flow direction is towards the converter module Maintenance 75 ...
Page 85: ...14 Open the installation stand optional and place it in front of the module 14 Maintenance 85 ...
Page 108: ...108 ...
Page 112: ...Description CAN bus connection XCAN XCAN 112 BCU x5 control unit ...
Page 116: ...116 Dimension drawings ...
Page 117: ...Dimension drawings 117 ...
Page 118: ...118 Dimension drawings ...
Page 130: ...130 ...