Implementing the undervoltage control (Power-loss
ride-through)
See the firmware manual.
Controlling a contactor between drive and motor
The control of the output contactor depends on how you use the drive, that is, which motor
control mode and which motor stop mode you select.
If you have the DTC motor control mode and the motor ramp stop mode selected, use this
operation sequence to open the contactor:
1.
Give a stop command to the drive.
2.
Wait until the drive decelerates the motor to zero speed.
3.
Open the contactor.
If you have the DTC motor control mode and the motor coast stop, or scalar control mode
selected, open the contactor as follows:
1.
Give a stop command to the drive.
2.
Open the contactor.
WARNING!
When the DTC motor control mode is in use, never open the output contactor while
the drive controls the motor. The DTC motor control operates extremely fast, much
faster than it takes for the contactor to open its contacts. When the contactor starts
opening while the drive controls the motor, the DTC control will try to maintain the
load current by immediately increasing the drive output voltage to the maximum.
This will damage, or even burn the contactor completely.
Implementing a bypass connection
If bypassing is required, employ mechanically or electrically interlocked contactors between
the motor and the drive and between the motor and the power line. Make sure with
interlocking that the contactors cannot be closed simultaneously. The installation must be
clearly marked as defined in IEC/EN 61800-5-1, subclause 6.5.3, for example, “THIS
MACHINE STARTS AUTOMATICALLY”.
WARNING!
Never connect the drive output to the electrical power network. The connection
may damage the drive.
Protecting the contacts of relay outputs
Inductive loads (relays, contactors, motors) cause voltage transients when switched off.
The relay contacts on the drive control unit are protected with varistors (250 V) against
overvoltage peaks. In spite of this, it is highly recommended that inductive loads are equipped
with noise attenuating circuits (varistors, RC filters [AC] or diodes [DC]) to minimize the
EMC emission at switch-off. If not suppressed, the disturbances may connect capacitively
or inductively to other conductors in the control cable and form a risk of malfunction in other
parts of the system.
80 Guidelines for planning the electrical installation
Summary of Contents for ACS880-04FXT
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 04FXT drive module packages Hardware manual ...
Page 2: ......
Page 4: ......
Page 40: ...40 ...
Page 54: ...54 ...
Page 82: ...82 ...
Page 86: ...M10 86 Electrical installation ...
Page 106: ...106 ...
Page 118: ...118 ...
Page 122: ...122 ...
Page 132: ...132 ...
Page 136: ...136 ...
Page 158: ...158 ...
Page 160: ...Standard configuration IP00 UL Type Open 160 Dimension drawings ...
Page 161: ...Drive module with optional support brackets IP00 UL Type Open Dimension drawings 161 ...
Page 163: ...Mounting plate opening 3AXD50000038119 Dimension drawings 163 ...
Page 164: ...3AXD50000038119 164 Dimension drawings ...
Page 182: ... Declaration of conformity 182 The Safe torque off function ...
Page 183: ...The Safe torque off function 183 ...
Page 184: ...184 ...