2×300
2×300
0960A-7
2×300
2×300
1080A-7
2×400
2×300
1320A-7
The cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire insulation at 40 °C
(104 °F) ambient temperature. Not more than three current-carrying conductors in raceway or cable or earth
(directly buried). For other conditions, dimension the cables according to local safety regulations, appropriate
input voltage and the load current of the drive.
1)
The table gives DC cable types when the cables are outside the cabinet. For DC cables inside the cabinet,
select a cable capable of carrying 2/3 of the continuous output current of one drive module.
*)
Connection (1× xxx): One phase conductor of the three-phase cable between the DC+ terminals of the drive
modules and another phase conductor of the three-phase cable between the DC- terminals of the drive
modules. The third phase conductor unconnected.
**)
Connection (2 × (3 × xxx)): two phase conductors of one three-phase cable between the DC+ terminals of
the drive modules and two phase conductors of the second three-phase cable between the DC- terminals
of the drive modules. The third phase conductors unconnected.
Terminal and entry data for the power cables
The maximum accepted cable size is 4×(3×240) mm
2
or 4×(3×500 AWG). Screw size for
connecting busbars to the drive module input and output busbars: M12, tightening torque
50…75 N·m.
■
Units without full-size output cable connection terminals and with a
common mode filter (+E208)
It is possible to use the maximum cable size (4×[3×240] mm
2
or 4 ×[(3×500 AWG]) only
with special cable lugs and additional insulation. For more information, contact your local
ABB representative.
Terminal data for the control cables
See section
Default I/O connection diagram (page 110)
Electrical power network specification
ACS880-04FXT-xxxx-3 drives: 380…415 VAC 3-phase +10%…-15%. This is in-
dicated in the type designation label as typical input voltage level 3~400 V AC.
Voltage (U
1
)
ACS880-04FXT-xxxx-5 drives: 380…500 V AC 3-phase +10%…-15%. This is in-
dicated in the type designation label as typical input voltage levels
3~400/480/500 V AC.
ACS880-04FXT-xxxx-7 drives: 525…690 V AC 3-phase +10%…-15%. This is in-
dicated in the type designation label as typical input voltage levels 3~525/600/690 V
AC.
TN (grounded) and IT (ungrounded) systems
Network type
Maximum allowable prospective short-circuit current is 65 kA when protected by
the fuses given in the fuse table.
Short-circuit withstand
strength (IEC 61439-1)
The drive is suitable for use on a circuit capable of delivering not more than
100,000 rms symmetrical amperes at 600 V maximum when protected by the fuses
given in the fuse table.
Short-circuit current
protection (UL 508A)
Technical data 149
Summary of Contents for ACS880-04FXT
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 04FXT drive module packages Hardware manual ...
Page 2: ......
Page 4: ......
Page 40: ...40 ...
Page 54: ...54 ...
Page 82: ...82 ...
Page 86: ...M10 86 Electrical installation ...
Page 106: ...106 ...
Page 118: ...118 ...
Page 122: ...122 ...
Page 132: ...132 ...
Page 136: ...136 ...
Page 158: ...158 ...
Page 160: ...Standard configuration IP00 UL Type Open 160 Dimension drawings ...
Page 161: ...Drive module with optional support brackets IP00 UL Type Open Dimension drawings 161 ...
Page 163: ...Mounting plate opening 3AXD50000038119 Dimension drawings 163 ...
Page 164: ...3AXD50000038119 164 Dimension drawings ...
Page 182: ... Declaration of conformity 182 The Safe torque off function ...
Page 183: ...The Safe torque off function 183 ...
Page 184: ...184 ...