![ABB ACS880-04FXT Hardware Manual Download Page 19](http://html.mh-extra.com/html/abb/acs880-04fxt/acs880-04fxt_hardware-manual_3309019.webp)
General safety in operation
These instructions are for all personnel that operate the drive.
WARNING!
Obey these instructions. If you ignore them, injury or death, or damage to the
equipment can occur.
•
Keep the cabinet doors closed when the drive is powered. With the doors open, a risk
of a potentially fatal electric shock, arc flash or high-energy arc blast exists.
•
If you have a cardiac pacemaker or other electronic medical device, keep away from
the area near motor, drive, and the drive power cabling when the drive is in operation.
There are electromagnetic fields present which can interfere with the function of such
devices. This can cause a health hazard.
•
Give a stop command to the drive before you reset a fault. If you have an external source
for the start command and the start is on, the drive will start immediately after the fault
reset, unless you configure the drive for pulse start. See the firmware manual.
•
Before you activate the automatic fault reset or automatic restart functions of the drive
control program, make sure that no dangerous situations can occur. These functions
reset the drive automatically and continue operation after a fault or supply break. If these
functions are activated, the installation must be clearly marked as defined in
IEC/EN 61800-5-1, subclause 6.5.3, for example, "THIS MACHINE STARTS
AUTOMATICALLY".
Note:
•
The maximum drive power cycles is five times in ten minutes. Power cycling the drive
too often can damage the charging circuit of the DC capacitors. If you need to start or
stop the drive, use the control panel keys or commands through the I/O terminals of the
drive.
•
If the drive is in remote control mode, you cannot stop or start the drive with the control
panel.
Additional instructions for permanent magnet motor drives
■
Safety in installation, start-up, maintenance
These are additional warnings concerning permanent magnet motor drives. The other safety
instructions in this chapter are also valid.
WARNING!
Obey these instructions. If you ignore them, injury or death, or damage to the
equipment can occur.
If you are not a qualified electrical professional, do not do installation or
maintenance work.
•
Do not do work on the drive when a rotating permanent magnet motor is connected to
it. A rotating permanent magnet motor energizes the drive including its input and output
power terminals.
Before installation, start-up and maintenance work on the drive:
•
Stop the drive.
•
Disconnect the motor from the drive with a safety switch or by other means.
Safety instructions 19
Summary of Contents for ACS880-04FXT
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 04FXT drive module packages Hardware manual ...
Page 2: ......
Page 4: ......
Page 40: ...40 ...
Page 54: ...54 ...
Page 82: ...82 ...
Page 86: ...M10 86 Electrical installation ...
Page 106: ...106 ...
Page 118: ...118 ...
Page 122: ...122 ...
Page 132: ...132 ...
Page 136: ...136 ...
Page 158: ...158 ...
Page 160: ...Standard configuration IP00 UL Type Open 160 Dimension drawings ...
Page 161: ...Drive module with optional support brackets IP00 UL Type Open Dimension drawings 161 ...
Page 163: ...Mounting plate opening 3AXD50000038119 Dimension drawings 163 ...
Page 164: ...3AXD50000038119 164 Dimension drawings ...
Page 182: ... Declaration of conformity 182 The Safe torque off function ...
Page 183: ...The Safe torque off function 183 ...
Page 184: ...184 ...