UL/NEC
1)
input and motor cabling
Drive type
ACS880-
04FXT-
…
Common cabling for the drive modules
3)
Cabling per drive module
2)
Al cable type
Cu cable type
Al cable type
Cu cable type
AWG/kcmil
AWG/kcmil
AWG/kcmil
AWG/kcmil
U
N
= 400 V
4×700 or 6×250
3×600 or 4×300
3×400 or 4×250
2×600 or 3×300
1008A-3
4×700 or 6×350
3×700 or 5×350
3×400 or 4×250
2×700 or 3×350
1188A-3
6×500
4×500 or 6×300
3×500 or 4×300
3×500 or 4×300
1330A-3
6×500
5×600 or 6×400
4×500
3×600 or 4×400
1610A-3
U
N
= 500 V
4×700 or 6×250
3×600 or 4×300
3×500 or 4×300
2×600 or 3×300
1008A-5
4×700 or 6×350
3×700 or 5×350
3×600 or 4×400
2×700 or 3×350
1158A-5
4×700 or 6×350
4×500 or 6×300
3×600 or 4×400
3×500 or 4×300
1310A-5
6×500
5×600 or 6×400
4×500
3×600 or 4×400
1610A-5
U
N
= 690 V
3×500 or 5×250
3×350 or 5×4/0
2×500 or 3×250
2×350 or 3×4/0
0808A-7
3×700 or 5×350
3×500 or 5×250
2×700 or 3×350
2×500 or 3×250
0960A-7
4×500 or 6×300
3×600 or 4×350
3×500 or 4×300
2×600 or 3×300
1080A-7
5×600 or 6×400
4×500 or 6×300
3×600 or 4×400
3×500 or 4×300
1320A-7
The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one
on top of the other, ambient temperature 30 °C (86 °F) PVC insulation, surface temperature 70 °C (158 °F)
(EN 60204-1 and IEC 60364-5-52). For other conditions, dimension the cables according to local safety
regulations, appropriate input voltage and the load current of the drive.
1)
See section
Drive connection examples (page 27)
2)
The supply cables are connected to a common switch or breaker, see section
. The whole input current flows through common cabling and you can use the recommended
cables for that. The connection from the switch to the drive modules inside the cabinet can be made with
busbars. Note that common output cables require the use of
d
u/d
t
filters.
3)
UL/NEC
1)
external
*)
DC cabling between drive modules
Drive type
ACS880-
04FXT-
…
Al cable type
**
Cu cable type
**
mm
2
mm
2
U
N
= 400 V
2×400
2×400
1008A-3
2×400
2×400
1188A-3
2×500
2×400
1330A-3
2×500
2×400
1610A-3
U
N
= 500 V
2×400
2×400
1008A-5
2×400
2×400
1158A-5
2×500
2×400
1310A-5
2×500
2×400
1610A-5
U
N
= 690 V
1×500
1×350
0808A-7
148 Technical data
Summary of Contents for ACS880-04FXT
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 04FXT drive module packages Hardware manual ...
Page 2: ......
Page 4: ......
Page 40: ...40 ...
Page 54: ...54 ...
Page 82: ...82 ...
Page 86: ...M10 86 Electrical installation ...
Page 106: ...106 ...
Page 118: ...118 ...
Page 122: ...122 ...
Page 132: ...132 ...
Page 136: ...136 ...
Page 158: ...158 ...
Page 160: ...Standard configuration IP00 UL Type Open 160 Dimension drawings ...
Page 161: ...Drive module with optional support brackets IP00 UL Type Open Dimension drawings 161 ...
Page 163: ...Mounting plate opening 3AXD50000038119 Dimension drawings 163 ...
Page 164: ...3AXD50000038119 164 Dimension drawings ...
Page 182: ... Declaration of conformity 182 The Safe torque off function ...
Page 183: ...The Safe torque off function 183 ...
Page 184: ...184 ...