7×(3×240)
6×(3×240)
4×(3×240)
3×(3×240)
1610A-5
U
N
= 690 V
4×(3×240)
4×(3×150)
3×(3×120)
3×(3×95)
0808A-7
5×(3×185)
4×(3×185)
3×(3×185)
3×(3×120)
0960A-7
5×(3×240)
4×(3×240)
3×(3×185)
3×(3×150)
1080A-7
6×(3×240)
5×(3×240)
4×(3×185)
3×(3×185)
1320A-7
The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one
on top of the other, ambient temperature 30 °C (86 °F) PVC insulation, surface temperature 70 °C (158 °F)
(EN 60204-1 and IEC 60364-5-52). For other conditions, dimension the cables according to local safety
regulations, appropriate input voltage and the load current of the drive.
1)
See section
Drive connection examples (page 27)
2)
The supply cables are connected to a common switch or breaker, see section
. The whole input current flows through common cabling and you can use the recommended
cables for that. The connection from the switch to the drive modules inside the cabinet can be made with
busbars.
3)
IEC
1)
external
*)
DC cabling between drive modules
Drive type
ACS880-
04FXT-
…
Al cable type
**
Cu cable type
**
mm
2
mm
2
U
N
= 400 V
2×(3×185)
2×(3×120)
1008A-3
2×(3×185)
2×(3×150)
1188A-3
2×(3×185)
2×(3×185)
1330A-3
2×(3×240)
2×(3×240)
1610A-3
U
N
= 500 V
2×(3×185)
2×(3×120)
1008A-5
2×(3×185)
2×(3×150)
1158A-5
2×(3×185)
2×(3×185)
1310A-5
2×(3×240)
2×(3×240)
1610A-5
U
N
= 690 V
2×(3×120)
2×(3×95)
0808A-7
2×(3×185)
2×(3×120)
0960A-7
2×(3×185)
2×(3×150)
1080A-7
2×(3×185)
2×(3×185)
1320A-7
The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one
on top of the other, ambient temperature 30 °C (86 °F) PVC insulation, surface temperature 70 °C (158 °F)
(EN 60204-1 and IEC 60364-5-52). For other conditions, dimension the cables according to local safety
regulations, appropriate input voltage and the load current of the drive.
1)
The table gives DC cable types when the cables are outside the cabinet. For DC cables inside the cabinet,
select a cable capable of carrying 2/3 of the continuous output current of one drive module.
*)
Connection (2 × (3 × xxx)): two phase conductors of one three-phase cable between the DC+ terminals of
the drive modules and two phase conductors of the second three-phase cable between the DC- terminals
of the drive modules. The third phase conductors unconnected.
**)
Technical data 147
Summary of Contents for ACS880-04FXT
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 04FXT drive module packages Hardware manual ...
Page 2: ......
Page 4: ......
Page 40: ...40 ...
Page 54: ...54 ...
Page 82: ...82 ...
Page 86: ...M10 86 Electrical installation ...
Page 106: ...106 ...
Page 118: ...118 ...
Page 122: ...122 ...
Page 132: ...132 ...
Page 136: ...136 ...
Page 158: ...158 ...
Page 160: ...Standard configuration IP00 UL Type Open 160 Dimension drawings ...
Page 161: ...Drive module with optional support brackets IP00 UL Type Open Dimension drawings 161 ...
Page 163: ...Mounting plate opening 3AXD50000038119 Dimension drawings 163 ...
Page 164: ...3AXD50000038119 164 Dimension drawings ...
Page 182: ... Declaration of conformity 182 The Safe torque off function ...
Page 183: ...The Safe torque off function 183 ...
Page 184: ...184 ...