![ABB ACS880-04FXT Hardware Manual Download Page 117](http://html.mh-extra.com/html/abb/acs880-04fxt/acs880-04fxt_hardware-manual_3309117.webp)
Make sure that …
The enclosures of the equipment in the cabinet have proper galvanic connection to the cabinet protective
earth (ground) busbar; The connection surfaces at the fastening points are bare (unpainted) and the
connections are tight, or separate grounding conductors have been installed.
The supply voltage matches the nominal input voltage of the drive. See the type designation label.
The input power cable has been connected to the appropriate terminals, the phase order is right, and
the terminals have been tightened. (Pull on the conductors to check.)
Appropriate AC fuses and a main disconnector have been installed.
The motor cable has been connected to the appropriate terminals, the phase order is right, and the
terminals have been tightened. (Pull on the conductors to check.)
The brake resistor (if present) has been connected to the appropriate terminals, and the terminals have
been tightened. (Pull on the conductors to check.)
The motor cable (and brake resistor cable, if present) has been routed away from other cables.
No power factor compensation capacitors have been connected to the motor cable.
The control cables (if any) have been connected to the appropriate terminals, and the terminals have
been tightened. (Pull on the conductors to check.)
If a drive bypass connection will be used: The direct-on-line contactor of the motor and the drive output
contactor are either mechanically or electrically interlocked, ie, cannot be closed simultaneously.
There are no tools, foreign objects or dust from drilling inside the drive.
All shrouds and cover of the motor connection box are in place. Cabinet doors have been closed.
The motor and the driven equipment are ready for start.
Installation checklist 117
Summary of Contents for ACS880-04FXT
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 04FXT drive module packages Hardware manual ...
Page 2: ......
Page 4: ......
Page 40: ...40 ...
Page 54: ...54 ...
Page 82: ...82 ...
Page 86: ...M10 86 Electrical installation ...
Page 106: ...106 ...
Page 118: ...118 ...
Page 122: ...122 ...
Page 132: ...132 ...
Page 136: ...136 ...
Page 158: ...158 ...
Page 160: ...Standard configuration IP00 UL Type Open 160 Dimension drawings ...
Page 161: ...Drive module with optional support brackets IP00 UL Type Open Dimension drawings 161 ...
Page 163: ...Mounting plate opening 3AXD50000038119 Dimension drawings 163 ...
Page 164: ...3AXD50000038119 164 Dimension drawings ...
Page 182: ... Declaration of conformity 182 The Safe torque off function ...
Page 183: ...The Safe torque off function 183 ...
Page 184: ...184 ...