Typical power cable sizes
The table below gives typical copper and aluminum cable types with concentric copper
shield for the drive modules with nominal current. See also section
data for the power cables (page 146)
.
US
2)
IEC
1)
ACS880-
04F-…
Al cable type
Cu cable type
Al cable type
Cu cable type
AWG/kcmil
AWG/kcmil
mm
2
mm
2
U
n
= 400 V
2×700 MCM or 3×350 MCM
2×500 MCM or 3×250 MCM
3×(3×150)
3×(3×95)
504A-3
3×400 MCM or 4×250 MCM
2×600 MCM or 3×300 MCM
3×(3×185)
3×(3×120)
584A-3
3×400 MCM or 4×250 MCM
2×700 MCM or 3×350 MCM
3×(3×240)
3×(3×150)
649A-3
3×500 MCM or 4×300 MCM
3×500 MCM or 4×300 MCM
4×(3×185)
3×(3×185)
725A-3
3×700 MCM or 4×500 MCM
3×600 MCM or 4×400 MCM
4×(3×240)
3×(3×240)
820A-3
4×500 MCM
3×600 MCM or 4×400 MCM
4×(3×240)
3×(3×240)
880A-3
U
n
= 500 V
2×600 MCM or 3×300 MCM
2×400 MCM or 3×4/0
3×(3×150)
3×(3×95)
459A-5
2×700 MCM or 3×350 MCM
2×500 MCM or 3×250 MCM
3×(3×150)
3×(3×95)
502A-5
3×500 MCM or 4×300 MCM
2×600 MCM or 3×300 MCM
3×(3×185)
3×(3×120)
582A-5
3×600 MCM or 4×400 MCM
2×700 MCM or 3×350 MCM
3×(3×240)
3×(3×150)
6354-5
3×600 MCM or 4×400 MCM
3×500 MCM or 4×300 MCM
4×(3×185)
3×(3×185)
715A-5
4×500 MCM
3×600 MCM or 4×400 MCM
4×(3×240)
3×(3×240)
820A-5
4×500 MCM
3×600 MCM or 4×400 MCM
4×(3×240)
3×(3×240)
880A-5
U
n
= 690 V
2×350 MCM or 3×4/0
2×250 MCM or 3×2/0
3×(3×120)
2×(3×120)
329A-7
2×400 MCM or 3×4/0
2×300 MCM or 3×3/0
3×(3×120)
2×(3×120)
369A-7
2×500 MCM or 3×250 MCM
2×350 MCM or 3×4/0
2×(3×120)
2×(3×95)
429A-7
2×600 MCM or 3×300 MCM
2×400 MCM or 3×4/0
3×(3×150)
3×(3×95)
470A-7
2×700 MCM or 3×350 MCM
2×500 MCM or 3×250 MCM
3×(3×185)
3×(3×120)
522A-7
3×500 MCM or 4×300 MCM
2×600 MCM or 3×300 MCM
3×(3×185)
3×(3×150)
590A-7
3×500 MCM or 4×300 MCM
2×700 MCM or 3×350 MCM
3×(3×240)
3×(3×150)
650A-7
3×600 MCM or 4×400 MCM
3×500 MCM or 4×300 MCM
4×(3×185)
3×(3×185)
721A-7
The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays
one on top of the other, ambient temperature 30 °C (86 °F) PVC insulation, surface temperature 70 °C
(158 °F) (EN 60204-1 and IEC 60364-5-52). For other conditions, dimension the cables according to
local safety regulations, appropriate input voltage and the load current of the drive.
1)
The cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire insulation at 40 °C
(104 °F) ambient temperature. Not more than three current-carrying conductors in raceway or cable
or earth (directly buried). For other conditions, dimension the cables according to local safety regula-
tions, appropriate input voltage and the load current of the drive.
2)
Temperature: For IEC, select a cable rated for at least 70 °C maximum permissible temperature of con-
ductor in continuous use. For North America, power cables must be rated for 75 °C (167 °F) or higher.
Voltage: 600 V AC cable is accepted for up to 500 V AC. 750 V AC cable is accepted for up to 600 V AC.
1000 V AC cable is accepted for up to 690 V AC.
Technical data 145
Summary of Contents for ACS880-04F-504A-3
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 04F drive modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 36: ...36 ...
Page 44: ...44 ...
Page 50: ...50 Mechanical installation ...
Page 56: ...56 ...
Page 116: ...116 ...
Page 122: ...4 3 2 122 Maintenance ...
Page 128: ...128 ...
Page 143: ... Package dimensions Package dimensions without IP shroud kit Technical data 143 ...
Page 158: ...158 ...
Page 160: ...Standard configuration IP20 UL Type Open 160 Dimension drawings ...
Page 161: ...Drive module with options E208 and H370 IP20 UL Type Open Dimension drawings 161 ...
Page 162: ...Drive module with options 0B051 E208 0H371 IP00 UL Type Open 162 Dimension drawings ...
Page 163: ...Drive module with options 0B051 E208 0H371 C217 IP00 UL Type Open Dimension drawings 163 ...
Page 164: ...Drive module with options 0B051 0H371 IP00 UL Type Open 164 Dimension drawings ...
Page 165: ...Mounting plate opening 3AXD50000038119 Dimension drawings 165 ...
Page 166: ...3AXD50000038119 166 Dimension drawings ...
Page 167: ...External control unit 3AXD50000011687 Dimension drawings 167 ...
Page 168: ...168 ...