Ambient conditions
Environmental limits for the drive are given below. The drive is to be used in a heated,
indoor, controlled environment or the heatsink can be placed outdoors when it is
protected according to these limitations.
Transportation
(in the protective pack-
age)
Storage
(in the protective pack-
age)
Operation
(installed for stationary
use)
-
-
For TN and TT neutral-
grounded network sys-
tems and IT non-corner-
grounded network sys-
tems: 0 to 4000 m
(13123 ft) above sea level
Installation site altitude
For corner-grounded
network systems: 0 to
2000 m (6561 ft) above
sea level
Above 1000 m (3281 ft):
see section
-40…+70 °C
(-40…+158 °F)
-40… 70 °C
(-40…+158 °F)
-15…+55 °C (5…131 °F).
No frost allowed. See
section
Surrounding air temper-
ature
Max. 95%
Max. 95%
5…95%
Relative humidity
No condensation allowed. Maximum allowed relative humidity is 60% in the
presence of corrosive gases.
IEC 60721-3-2:1997
IEC 60721-3-1:1997
IEC/EN 60721-3-3:2002
Contamination levels
Class 2C2
Class 1C2
Class 3C2
Chemical gases
Class 2S2
Class 1S3. (packing must
support this, otherwise
1S2)
Class 3S2. No conductive
dust allowed.
Solid particles
2
Pollution degree
IEC/EN 60664-1
60…106 kPa (0.6 … 1.05
atmospheres)
70…106 kPa (0.7 … 1.05
atmospheres)
70…106 kPa (0.7 … 1.05
atmospheres)
Atmospheric pressure
Max. 3.5 mm (0.14 in)
(2…9 Hz), max. 15 m/s
2
(49 ft/s
2
) (9…200 Hz) si-
nusoidal
Max. 1 mm (0.04 in) (5 …
13.2 Hz), max. 7 m/s
2
(23 ft/s
2
) (13.2…100 Hz)
sinusoidal
Max. 0.1 mm (0.004 in)
(10…57 Hz), max.
10 m/s
2
(33 ft/s
2
)
(57…150 Hz) sinusoidal
Vibration
IEC 60068-2-6:2007,
EN 60068-2-6:2008
With packing max.
100 m/s
2
(330 ft/s
2
),
11 ms
With packing max.
100 m/s
2
(330 ft/s
2
),
11 ms
Not allowed
Shock
IEC 60068-2-27:2008,
EN 60068-2-27:2009
100 mm (4 in) for weight
over 100 kg (220 lb)
100 mm (4 in) for weight
over 100 kg (220 lb)
Not allowed
Free fall
150 Technical data
Summary of Contents for ACS880-04F-504A-3
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 04F drive modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 36: ...36 ...
Page 44: ...44 ...
Page 50: ...50 Mechanical installation ...
Page 56: ...56 ...
Page 116: ...116 ...
Page 122: ...4 3 2 122 Maintenance ...
Page 128: ...128 ...
Page 143: ... Package dimensions Package dimensions without IP shroud kit Technical data 143 ...
Page 158: ...158 ...
Page 160: ...Standard configuration IP20 UL Type Open 160 Dimension drawings ...
Page 161: ...Drive module with options E208 and H370 IP20 UL Type Open Dimension drawings 161 ...
Page 162: ...Drive module with options 0B051 E208 0H371 IP00 UL Type Open 162 Dimension drawings ...
Page 163: ...Drive module with options 0B051 E208 0H371 C217 IP00 UL Type Open Dimension drawings 163 ...
Page 164: ...Drive module with options 0B051 0H371 IP00 UL Type Open 164 Dimension drawings ...
Page 165: ...Mounting plate opening 3AXD50000038119 Dimension drawings 165 ...
Page 166: ...3AXD50000038119 166 Dimension drawings ...
Page 167: ...External control unit 3AXD50000011687 Dimension drawings 167 ...
Page 168: ...168 ...