Residual current device compatibility
The drive is suitable for use with residual current devices of Type B.
Note: As standard, the drive contains capacitors connected between the main circuit
and the frame. These capacitors and long motor cables increase the ground leakage
current and may cause nuisance faults in residual current devices.
Connecting drive modules to a common DC system
See
ACS880-01 drives and ACS880-04 drive modules common DC systems application
guide (3AUA0000127818 [English])
Implementing a motor temperature sensor connection
WARNING!
IEC 61800-5-1 requires double or reinforced insulation between live parts and
accessible parts when:
•
the accessible parts are not conductive, or
•
the accessible parts are conductive, but not connected to the protective
earth.
Obey this requirement when you plan the connection of the motor temperature
sensor to the drive.
You have these implementation alternatives:
1.
If there is double or reinforced insulation between the sensor and the live parts
of the motor: You can connect the sensor directly to the analog/digital input(s)
of the drive. See the control cable connection instructions. Make sure that the
voltage does not exceed the maximum allowed voltage over the sensor.
2.
If there is basic insulation between the sensor and the live parts of the motor, or
if the insulation type is not known, you can connect the sensor to the drive via an
option module. The sensor and the module must form a double or reinforced
insulation between the motor live parts and the drive control unit. See
a motor temperature sensor to the drive through an option module (page 76)
Make sure that the voltage does not exceed the maximum allowed voltage over
the sensor.
3.
If there is basic insulation between the sensor and the live parts of the motor, or
if the insulation type is not known: You can connect a sensor to a digital input of
the drive via an external relay. The sensor and the relay must form a double or
reinforced insulation between the motor's live parts and the digital input of the
drive. Make sure that the voltage does not exceed the maximum allowed voltage
over the sensor.
■
Connecting a motor temperature sensor to the drive through an
option module
This table shows:
•
option module types that you can use for the motor temperature sensor connection
•
insulation or isolation level that each option module forms between its temperature
sensor connector and other connectors
76 Guidelines for planning the electrical installation
Summary of Contents for ACS880-04F-504A-3
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 04F drive modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 36: ...36 ...
Page 44: ...44 ...
Page 50: ...50 Mechanical installation ...
Page 56: ...56 ...
Page 116: ...116 ...
Page 122: ...4 3 2 122 Maintenance ...
Page 128: ...128 ...
Page 143: ... Package dimensions Package dimensions without IP shroud kit Technical data 143 ...
Page 158: ...158 ...
Page 160: ...Standard configuration IP20 UL Type Open 160 Dimension drawings ...
Page 161: ...Drive module with options E208 and H370 IP20 UL Type Open Dimension drawings 161 ...
Page 162: ...Drive module with options 0B051 E208 0H371 IP00 UL Type Open 162 Dimension drawings ...
Page 163: ...Drive module with options 0B051 E208 0H371 C217 IP00 UL Type Open Dimension drawings 163 ...
Page 164: ...Drive module with options 0B051 0H371 IP00 UL Type Open 164 Dimension drawings ...
Page 165: ...Mounting plate opening 3AXD50000038119 Dimension drawings 165 ...
Page 166: ...3AXD50000038119 166 Dimension drawings ...
Page 167: ...External control unit 3AXD50000011687 Dimension drawings 167 ...
Page 168: ...168 ...