This table shows examples of methods for wiring the drive. Refer to NFPA 70 (NEC)
along with state and local codes for the appropriate methods for your application.
Notes
Wiring method
Conduit - Metallic
1) 2)
Prefer symmetrical shielded VFD cable.
Electrical metallic tubing: Type EMT
Use separate conduit run for each motor.
Rigid metal conduit: Type RMC
Do not run input power wiring and motor wiring in
the same conduit.
Liquid-tight flexible metal electrical conduit: Type
LFMC
Conduit - Non-metallic
3)
Prefer symmetrical shielded VFD cable.
Liquid-tight flexible non-metallic conduit: Type LFNC
Use separate conduit run for each motor.
Do not run input power wiring and motor wiring in
the same conduit.
Wireways
Prefer symmetrical shielded VFD cable.
Metallic
Separate motor wiring from input power wiring and
other low voltage wiring.
Do not run outputs of multiple drives parallel. Bundle
each cable (wiring) together and use separators
where possible.
Free air
Prefer symmetrical shielded VFD cable.
Enclosures, air handlers, etc.
Allowed internally in enclosures when in accordance
with UL.
1) Metallic conduit may be used as an additional ground path, provided this path is a solid path capable of handling
ground currents.
2) See NFPA NFPA 70 (NEC), UL, and local codes for your application.
3) Non-metallic conduit use underground is allowed; however, these installations inherently have an increased chance
for nuisance problems due to the potential for water/moisture in the conduit. Water/moisture in the conduit
increases the likelihood of VFD faults or warnings. Proper installation is required to make sure there is no intrusion
of water/moisture.
Metal conduit
Couple separate parts of a metal conduit together: bridge the joints with a ground
conductor bonded to the conduit on each side of the joint. Also bond the conduits to
the drive enclosure and motor frame. Use separate conduits for input power, motor,
brake resistor, and control wiring. Do not run motor wiring from more than one drive
in the same conduit.
■
Power cable shield
If the cable shield is used as the sole protective earth (PE) conductor, make sure that
its conductivity agrees with the PE conductor requirements.
To effectively suppress radiated and conducted radio-frequency emissions, the cable
shield conductivity must be at least 1/10 of the phase conductor conductivity. The
requirements are easily met with a copper or aluminum shield. The minimum
requirement of the motor cable shield of the drive is shown below. It consists of a
concentric layer of copper wires with an open helix of copper tape or copper wire. The
better and tighter the shield, the lower the emission level and bearing currents.
68 Guidelines for planning the electrical installation
Summary of Contents for ACS880-04F-504A-3
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 04F drive modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 36: ...36 ...
Page 44: ...44 ...
Page 50: ...50 Mechanical installation ...
Page 56: ...56 ...
Page 116: ...116 ...
Page 122: ...4 3 2 122 Maintenance ...
Page 128: ...128 ...
Page 143: ... Package dimensions Package dimensions without IP shroud kit Technical data 143 ...
Page 158: ...158 ...
Page 160: ...Standard configuration IP20 UL Type Open 160 Dimension drawings ...
Page 161: ...Drive module with options E208 and H370 IP20 UL Type Open Dimension drawings 161 ...
Page 162: ...Drive module with options 0B051 E208 0H371 IP00 UL Type Open 162 Dimension drawings ...
Page 163: ...Drive module with options 0B051 E208 0H371 C217 IP00 UL Type Open Dimension drawings 163 ...
Page 164: ...Drive module with options 0B051 0H371 IP00 UL Type Open 164 Dimension drawings ...
Page 165: ...Mounting plate opening 3AXD50000038119 Dimension drawings 165 ...
Page 166: ...3AXD50000038119 166 Dimension drawings ...
Page 167: ...External control unit 3AXD50000011687 Dimension drawings 167 ...
Page 168: ...168 ...