Requirements for non-ABB motors,
P
n
> 100 kW (134 hp)
See also
Requirement for
Nominal AC line
voltage
Motor type
ABB d
u/dt and common mode filters, insulated
N-end motor bearings
Motor insula-
tion system
P
n
≥ 350 kW
or
frame size ≥ IEC 400
100 kW ≤
P
n
< 350 kW
or
IEC 315 ≤ frame size <
IEC 400
P
n
≥ 469 hp
or
frame size > NEMA 580
134 hp ≤
P
n
< 469 hp
or
NEMA 500 ≤ frame size
≤ NEMA 580
+ N + CMF
+ N or CMF
Standard:
Û
LL
= 1300 V
U
n
≤ 420 V
Random-wound and
form-wound
+ N + d
u/dt + CMF
+ d
u/dt + (N or CMF)
Standard:
Û
LL
= 1300 V
420 V <
U
n
≤ 500 V
+ N + CMF
+ N or CMF
Reinforced:
Û
LL
= 1600 V,
0.2 µs rise
time
+ N + d
u/dt + CMF
+ d
u/dt + (N or CMF)
Reinforced:
Û
LL
= 1600 V
500 V <
U
n
≤ 600 V
+ N + CMF
+ N or CMF
Reinforced:
Û
LL
= 1800 V
+ N + d
u/dt + CMF
+ d
u/dt + N
Reinforced:
Û
LL
= 1800 V
600 V <
U
n
≤ 690 V
+ N + CMF
+ N + CMF
Reinforced:
Û
LL
= 2000 V,
0.3 µs rise
time
1)
1) If the intermediate DC circuit voltage of the drive is increased from the nominal level due to long term resistor
braking cycles, check with the motor manufacturer if additional output filters are needed.
Abbreviations
Definition
Abbr.
Nominal AC line voltage
U
n
Peak line-to-line voltage at motor terminals which the motor insulation must
withstand
Û
LL
Motor nominal power
P
n
d
u/dt filter at the output of the drive
d
u/dt
Common mode filter of the drive
CMF
N-end bearing: insulated motor non-drive end bearing
N
Motors of this power range are not available as standard units. Consult the motor
manufacturer.
n.a.
62 Guidelines for planning the electrical installation
Summary of Contents for ACS880-04F-504A-3
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 04F drive modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 36: ...36 ...
Page 44: ...44 ...
Page 50: ...50 Mechanical installation ...
Page 56: ...56 ...
Page 116: ...116 ...
Page 122: ...4 3 2 122 Maintenance ...
Page 128: ...128 ...
Page 143: ... Package dimensions Package dimensions without IP shroud kit Technical data 143 ...
Page 158: ...158 ...
Page 160: ...Standard configuration IP20 UL Type Open 160 Dimension drawings ...
Page 161: ...Drive module with options E208 and H370 IP20 UL Type Open Dimension drawings 161 ...
Page 162: ...Drive module with options 0B051 E208 0H371 IP00 UL Type Open 162 Dimension drawings ...
Page 163: ...Drive module with options 0B051 E208 0H371 C217 IP00 UL Type Open Dimension drawings 163 ...
Page 164: ...Drive module with options 0B051 0H371 IP00 UL Type Open 164 Dimension drawings ...
Page 165: ...Mounting plate opening 3AXD50000038119 Dimension drawings 165 ...
Page 166: ...3AXD50000038119 166 Dimension drawings ...
Page 167: ...External control unit 3AXD50000011687 Dimension drawings 167 ...
Page 168: ...168 ...