AI1+
AI1-
AO1
AGND
2
1
3
T
T
T
One, two or three Pt100, Pt1000 or PTC sensors; or one KTY84 sensor
1
Set the input type to voltage with the appropriate switch or jumper on the control unit. Make the
corresponding setting in the control program in parameter group 12 Standard AI.
2
Select the excitation mode in parameter group 13 Standard AO.
3
WARNING!
As the inputs pictured above are not insulated according to IEC/EN 60664, the
connection of the motor temperature sensor requires double or reinforced
insulation between motor live parts and the sensor.
WARNING!
Make sure that the excitation current does not exceed the maximum permitted
current of the Pt100/Pt1000 sensor.
■
DIIL input
The DIIL input is used for the connection of safety circuits. The input is parametrized
to stop the unit when the input signal is lost.
Note: This input is not SIL or PL certified.
■
The XD2D connector
The XD2D connector provides an RS-485 connection that can be used for
•
basic master/follower communication with one master drive and multiple
followers,
•
fieldbus control through the embedded fieldbus interface (EFB), or
•
drive-to-drive (D2D) communication implemented by application programming.
See the firmware manual of the drive for the related parameter settings.
Enable bus termination on the units at the ends of the drive-to-drive link. Disable bus
termination on the intermediate units.
Use a high-quality shielded twisted-pair cable for the wiring, fro exmple, Belden 9842.
The nominal impedance of the cable should be 100…165 ohm. You can use one pair
for the data wiring and another pair or a wire for the grounding. Avoid unnecessary
loops and parallel runs near power cables.
The following diagram shows the wiring between control units.
106 Control unit of the drive
Summary of Contents for ACS880-04F-504A-3
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 04F drive modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 36: ...36 ...
Page 44: ...44 ...
Page 50: ...50 Mechanical installation ...
Page 56: ...56 ...
Page 116: ...116 ...
Page 122: ...4 3 2 122 Maintenance ...
Page 128: ...128 ...
Page 143: ... Package dimensions Package dimensions without IP shroud kit Technical data 143 ...
Page 158: ...158 ...
Page 160: ...Standard configuration IP20 UL Type Open 160 Dimension drawings ...
Page 161: ...Drive module with options E208 and H370 IP20 UL Type Open Dimension drawings 161 ...
Page 162: ...Drive module with options 0B051 E208 0H371 IP00 UL Type Open 162 Dimension drawings ...
Page 163: ...Drive module with options 0B051 E208 0H371 C217 IP00 UL Type Open Dimension drawings 163 ...
Page 164: ...Drive module with options 0B051 0H371 IP00 UL Type Open 164 Dimension drawings ...
Page 165: ...Mounting plate opening 3AXD50000038119 Dimension drawings 165 ...
Page 166: ...3AXD50000038119 166 Dimension drawings ...
Page 167: ...External control unit 3AXD50000011687 Dimension drawings 167 ...
Page 168: ...168 ...