Technical data
162
Efficiency
> 97% (at rated current and nominal supply voltage)
Degree of protection
IP42 (UL Type 1), IP54, (UL Type 12)
Ambient conditions
Environmental limits for the drive are given below. The drive must be used in a heated,
indoor controlled environment.
Operation
installed for stationary use
Storage
in the protective package
Transportation
in the protective package
Installation site altitude
0 to 4000 m (13123 ft) above
sea level. 690 V units: 0 to
2000 m (6562 ft) above sea
level. Above 1000 m (3281
ft), see
on page
-
-
Air temperature
0…+55° (+32…+131°F), no
frost allowed
[above +45°C (+113°F), see
on page
]
-40…+70°C (-40 to +158°F) -40…+70°C (-40 to +158°F)
Relative humidity
5 to 95%
Max. 95%
Max. 95%
No condensation allowed. Maximum allowed relative humidity is 60% in the presence of
corrosive gases.
Contamination levels
(IEC60721-3-3, IEC60721-3-2,
IEC60721-3-1)
No conductive dust allowed.
Boards with coating:
Chemical gases: Class 3C2
Solid particles: Class 3S2
Boards with coating:
Chemical gases: Class 1C2
Solid particles: Class 1S3
Boards with coating:
Chemical gases: Class 2C2
Solid particles: Class 2S2
Atmospheric pressure
70 to 106 kPa
0.7 to 1.05 atmospheres
70 to 106 kPa
0.7 to 1.05 atmospheres
60 to 106 kPa
0.6 to 1.05 atmospheres
Vibration
Marine requirements
±1 mm (peak value,
2…13.2 Hz)
0.7g (13.2 - 100 Hz)
Max. amplification 10
IEC 60068-2-6
0,075 mm (0…58 Hz)
10 m/s
2
(58…150Hz)
Max. amplification 10
1M2, IEC 60721-3-1
1.5 mm (2…9 Hz)
5 m/s
2
(9…200 Hz)
2M2, IEC 60721-3-2
3,5 mm (2…9 Hz)
10 m/s
2
(9…200 Hz)
Random 10-200 Hz,
acceleration spectral density
1 m2/s³
Shock (IEC 60068-2-29)
Not allowed
Max. 100 m/s
2
(330 ft./s
2
),
11 ms
Max. 100 m/s
2
(330 ft./s
2
),
11 ms
Free fall
Not allowed
100 mm (4 in.) for weight
over 100 kg (220 lb.)
100 mm (4 in.) for weight
over 100 kg (220 lb.)
Materials
Cabinet
Hot-dip zinc-coated (thickness approx. 20 µm) steel sheet (thickness 1.5 mm) with
polyester thermosetting powder coating (thickness approx. 80 µm) on visible surfaces
except back panel. Colour: RAL 7035 (light beige, semigloss).
Busbars
Tin- or silver-plated copper
Summary of Contents for ACS800-17LC
Page 1: ...ABB industrial drives Hardware manual ACS800 17LC Drives 55 to 5200 kW ...
Page 4: ......
Page 10: ...Update notice 6 ...
Page 18: ...Table of contents 12 ...
Page 26: ...Safety instructions 20 ...
Page 32: ...Introduction to the manual 26 ...
Page 60: ...Hardware description 54 ...
Page 74: ...Mechanical installation 68 ...
Page 114: ...Electrical installation 108 ...
Page 142: ...Maintenance 136 ...
Page 150: ...Internal cooling circuit 144 ...
Page 179: ...Dimensions 173 Frame sizes R7i R7i and R8i R8i bottom entry exit ...
Page 180: ...Dimensions 174 Frame sizes R7i R7i and R8i R8i marine units C121 ...
Page 182: ...www abb com drives www abb com drivespartners Contact us 3AUA0000065339 Rev B EN 2016 06 07 ...