Planning the electrical installation
74
Sine filters
Sine filters protect the motor insulation system. Therefore, a du/dt filter can be replaced with a sine
filter. The peak phase-to-phase voltage with a sine filter is approximately 1.5 ×
U
N
.
Selecting the power cables
General rules
Dimension the input power and motor cables
according to local regulations
:
• Dimension the cable to carry the drive load current. See chapter
Technical data
for the rated currents.
• Select a cable rated for at least 70
°
C maximum permissible temperature of
conductor in continuous use. For US, see
page
.
• The inductance and impedance of the PE conductor/cable (grounding wire) must
be rated according to permissible touch voltage appearing under fault conditions
(so that the fault point voltage will not rise excessively when a ground fault
occurs).
• 600 V AC cable is accepted for up to 500 V AC. For 690 V AC rated equipment,
the rated voltage between the conductors of the cable should be minimum 1 kV.
Use symmetrical shielded motor cable, see page
. Ground the shield(s) of motor
cable(s) 360° at both ends.
Note:
When continuous metal conduit is employed, shielded cable is not required.
The conduit must have bonding at both ends as with cable shield.
A four-conductor system is allowed for input cabling, but shielded symmetrical cable
is recommended.
Û
LL
/
U
N
Without du/dt Filter
Cable length (m)
du/dt
U
N
-------------(1/
μ
s)
1.0
2.0
5.0
4.0
3.0
1.5
2.5
3.5
4.5
100
200
300
100
200
300
0.0
0.5
1.0
1.5
2.0
2.5
3.0
Cable length (m)
With du/dt Filter
du/dt
U
N
-------------(1/
μ
s)
Û
LL
/
U
N
5.5
Summary of Contents for ACS800-17LC
Page 1: ...ABB industrial drives Hardware manual ACS800 17LC Drives 55 to 5200 kW ...
Page 4: ......
Page 10: ...Update notice 6 ...
Page 18: ...Table of contents 12 ...
Page 26: ...Safety instructions 20 ...
Page 32: ...Introduction to the manual 26 ...
Page 60: ...Hardware description 54 ...
Page 74: ...Mechanical installation 68 ...
Page 114: ...Electrical installation 108 ...
Page 142: ...Maintenance 136 ...
Page 150: ...Internal cooling circuit 144 ...
Page 179: ...Dimensions 173 Frame sizes R7i R7i and R8i R8i bottom entry exit ...
Page 180: ...Dimensions 174 Frame sizes R7i R7i and R8i R8i marine units C121 ...
Page 182: ...www abb com drives www abb com drivespartners Contact us 3AUA0000065339 Rev B EN 2016 06 07 ...